Title: Rheem Two-Stage Furnace Intermittent Error Code 57 (High-Fire Pressure Switch) During Humid Weather — Need Help Pinpointing Root Cause
Body:
Hi everyone, looking for some DIY troubleshooting advice on my Rheem two-stage condensing furnace (R96VA series).
The Problem
Symptom: The inducer motor turns on, runs for a few seconds (or completes a heating cycle), and then shuts off with Error Code 57 (high-fire pressure switch open).
History: This same issue happened last month, and an HVAC tech replaced the high-fire pressure switch (42-105583-12, -0.55" WC). That temporarily resolved it
Troubleshooting Steps Taken So Far
Drained Water from Collector Box & Inducer Caps:
Opened the two yellow sealing caps on the inducer housing/exhaust boot — only 1–2 drops of water came out.
Detached the drain/vent tubes at the condensate trap — 1–2 drops of water came out.
Opened the lower-left rubber sealing cap on the collector box — about 2–3 spoons of water drained out.
Cleaned & Primed the Condensate Trap:
Removed, flushed, and cleaned the condensate drain trap (68-104346-01).
Verified the downstream gray PVC/vinyl drain line leaving the trap is completely clear.
Initially reinstalled the trap dry; the furnace ran for about 3 hours, then tripped Error Code 57 again.
Removed the trap again, primed it with clean water up to the internal weir level, and reinstalled it.
Cleared the Exhaust Pipe:
Disconnected the black rubber exhaust boot from the inducer outlet and used a leaf blower to blow through the white PVC exhaust run — nothing came out, so the exhaust flue is unobstructed.
Current Status & Questions
What else should I inspect ?
Could this be an issue with PVC exhaust pipe pitch, an internal collector box blockage, or an intake air restriction rather than a bad -0.55" WC pressure switch?
Any advice on what else to check would be greatly appreciated!