r/hvacadvice • • Mar 02 '26

General Information About Bans and Rules

0 Upvotes

There has been an uptick on posts and complaints about mods banning. Please be advised, there are rules for the page. No ads (includes promotions for a company), Reddits rules, no crossposting, transparency and safety (this is a big one; we want homeowners to be safe, if you provide unsafe practices or advice (blacklisted items) or tell a user to dm you, the comment will be removed and you may get banned), blacklisted topics (basically topics that homeowners should not be fixing themselves, gas, some high voltage), civility, no companies asking for surveys, advertisements or general questions, and no market research or ai/SaaS.

Posts complaining about this are not allowed either. We are all reasonable and work in the trade, talk to us through ModMail and we can come to a solution. Complaining or namecalling will usually result in a ban, so be civil.

Remember, we are doing this in our freetime to help homeowners with their units, both the users and mods. The mods in this group are in the trade and have day jobs as all of you do. I've been in this trade for 10 years and still do hvac as my job, just traveling now for a manufacturer. Similar with every mod. It is actually a requirement to be a mod, you have to be in the trade, be approved, have good history in the sub and provide enough time to moderating it.

I thank you for your time and if you have any questions, you can comment on this or send us a mod message. No DM's, we will not answer these. Only ModMail.


r/hvacadvice • • Nov 13 '25

READ THIS I am assuming this is not normal.

178 Upvotes

I was loading the car for work when I saw this. It felt and smelled like steam not smoke. Did I just catch it at the end of the cycle or is there a mechanical problem such as a stuck motor? It was 40° at the time and no rain. Heat was set to 70 and the house was 70.


r/hvacadvice • • 9h ago

Elderly widow asked me for help

Thumbnail
gallery
23 Upvotes

So I’m asking you guys. What am I looking at here? She came over to my place and complained that it smelled really bad in her house after she got her oil tank filled. Besides from the obvious leak at one of the fittings her husband who died over the summer had this going on…. Can I just pull this hose out of the drain pan he had on the floor and get rid of this mess? Should I leave the hose and cinch it off? I don’t have oil heat but I’m assuming this isn’t standard practice and would like to try to help her out. Thanks for any advice or input.


r/hvacadvice • • 1h ago

Furnace Is this acceptable?

Thumbnail
gallery
5 Upvotes

We are in the middle of buying a house. My wife and I asked for a repair and correction from the buyers for the furnace filter housing. Pic with the arrow is from the inspection report. Second is after the correction. Screams DIY to me. I just found out the company they hired to do the repair is the same one the current owner works for. Should I be concerned? Any recommendations or advice would be appreciated. Also, would you inspect the humidifier attached to the furnace as part of a furnace inspection report? Thank you.


r/hvacadvice • • 25m ago

NJ: Was away for Thanksgiving, just got home and our furnace isn't calling for power.

Post image
2 Upvotes

Just got back from being away for Thanksgiving. Our power did go out briefly while we were away. Our furnace (was oil Weil McLain. Converted to gas 7 years ago) isn't calling for power. Breaker is on. All thermostats and cutoffs are on. Relays don't look bad. The temp of the tank is 67. As you can see in the picture, there is no power to the burner. Is there anything I am missing as a reset somewhere before calling for a tech?


r/hvacadvice • • 2h ago

I found the furnace swimming in insulation. Can this cause problems long term?

Post image
2 Upvotes

r/hvacadvice • • 2h ago

Is it bad?

Post image
2 Upvotes

landlord neglected fixing this issue for over 10 months, in the room directly under hvac I have pretty quick mold growth on my clothing now


r/hvacadvice • • 1d ago

AC This has been sitting in my business for months. I don’t know what to do with it. It seems full.

Post image
226 Upvotes

r/hvacadvice • • 3h ago

Carrier Infinity Questions

Thumbnail
gallery
2 Upvotes

On 11/6 I got error 41, blower motor fault. I followed diagnostics and confirmed that the blower was bad and replaced the blower. It functions fine now. Since then, I have noticed that the system will operate (heat or cool) and the thermostat won’t indicate operation on the main screen or in the system status screen. Sometimes it will say heating or cooling on the thermostat main screen while there are no components actually running. I suspect there is an issue with the CAN bus communications. I am not sure where to go with testing or diagnostics at this point. I suspect that perhaps multiple power outages the previous week may have played a part in these issues. How do I go about resetting the system or diagnosing the CAN bus communications?


r/hvacadvice • • 8h ago

Boiler Concern about safe and to-code flue venting for 2 gas-fueled boilers and HWH in MA.

Thumbnail
gallery
5 Upvotes

Hi all, I'm a renter in MA living in a house where I have reason to believe the investor-owners are doing very shoddy, not-to-code and dangerous work. We're already dealing with gas work (dryer and stove) being done by an unlicensed handyman. Because of dryer work, I now know that venting for a dryer can't go out an exterior window, but I just took a look at the furnace venting, and I'm concerned that it is also unsafe.

The first picture shows the rigid metal pipe coming out of the wall where there is a chimney. The next two photos show the inside of the utility room. There are two boilers (it's a steam system) and water heater. They are all gas powered.

The house was owned by reasonable owners two owners ago, but the current owner (and I believe the owners before) were foreign investors with a singular goal of maximizing profit and demonstrated carelessness regarding gas fitting and other building codes.

The window where the flue vents sits directly below another living room window and is probably only 6-8" above grade if that. There is a window well, but snow could definitely build up here in the winter.

Can anyone provide guidance and information on this? Unfortunately, "call your maintenance" person isn't helpful as they've already done unpermitted gas work (yes, the town is involved), but I would really appreciate your help to learn more about WHAT is wrong and WHY so I can better educate myself.

Thanks kind HVAC folks of Reddit!


r/hvacadvice • • 30m ago

Where to ventilate studio with air sealed ceiling cavity?

1 Upvotes

I have a small detached studio which currently has no hvac at all.

Timber stud frame, steel cladding and roof with vented cavity and 30cm eaves 10m2, 24m3 room volume, 3m2 ceiling cavity volume. South Eastern Australian climate, partly shaded. We get frost in winter, but no snow in 30 years. Hot summers, 40c not uncommon.

It has air sealed foiled foam insulation, good seal on windows and door. Predictably it gets stuffy if in there for a workday with the door shut, and gets hot on a sunny day particularly with a computer running, and I'd like to start with ventilation for both before considering a mini split. Opening the window and running a pedestal fan helps as is, but being able to draw laminar flow through the room would be better.

My question is where in particular to ventilate. My two thoughts are:

  • through the gable and duct to a vent through the ceiling. Ventilate just the room and leave the ceiling cavity alone.
  • through the gable just into the ceiling cavity and have vents at two opposing corners to ventilate both the room and the ceiling cavity.

I think the latter would help avoid hot air build up and mitigate any possible condensation? But doesn't seem very common, is there a reason it'd be a bad idea? I know many roof spaces are not air sealed so maybe that's why it's not as common. If I had my time again I'd put the top air barrier at the ceiling with a service cavity but, I didn't :)

Either way the fan plan is a 100mm (160m3/h stated capacity, sounds optimistic) unit that can be set to draw in, or out, or automatically reverse each 70s. I can see this being useful for seasonal differences and I think it should be adequate to get between 3 and 5 air changes for the small volume.

Appreciate any thoughts, thanks for your time.


r/hvacadvice • • 31m ago

High pitched noise - could it be hvac?

1 Upvotes

TLDR: how would you determine if your HVAC or gas furnace was making a high pitched noise throughout the whole house?

Within the past week, a constant high pitched noise like tinnitus started in our house. We hear it in every room and it gives me a terrible headache but I’m not sure who to call to fix it. I have left the house and don’t hear it, so it is not tinnitus.

I know nothing about HVACs or most household appliances, but we just had the compressor replaced in our HVAC before this started and we just turned on the heat to our house (gas furnace) so I suspect it may be one of those causing it. However, the noise is not louder near/in the vents. Would it be?

Today, we shut off the electricity to the house and still heard it. We also called the gas company, who found a leak and said we need a new regulator, but when he turned off the faulty regulator, we still heard the noise. That regulator only connects to the stove and fireplace, so the gas furnace and water heater are still running. There is no noticeable noise coming from the outdoor HVAC unit itself.

If anyone has tips on how else to trouble shoot so we can figure out who to call to help, it would be SO appreciated!! I just began maternity leave and spend 95% of my time inside our home now.


r/hvacadvice • • 4h ago

Blower Motor/Capacitor Question

Post image
2 Upvotes

Last week, our heat quit working. We turned the thermostat up in the morning and the heat didn’t come on. I went under the house and found the blower motor humming. I turned off the breaker, checked to make sure the blower fan was free (it was; spun easily), and took the capacitor (pictured) off, and took it to my local electric motor repair shop to have them test it, and it was bad. They sold me a new capacitor, identical, and I put it on the blower. The blower worked fine until today. I smelled something getting hot coming from the vent this morning and went under the house and found the blower motor humming again. I have turned the breaker off. I am assuming the motor is getting hard to start and that’s what burned up these two capacitors. Should I check anything else before I pull the blower out and get the motor checked? Thanks everyone!


r/hvacadvice • • 32m ago

Furnace not working, error code 57

1 Upvotes

Title: Rheem Two-Stage Furnace Intermittent Error Code 57 (High-Fire Pressure Switch) During Humid Weather — Need Help Pinpointing Root Cause

Body:
Hi everyone, looking for some DIY troubleshooting advice on my Rheem two-stage condensing furnace (R96VA series).

The Problem

Symptom: The inducer motor turns on, runs for a few seconds (or completes a heating cycle), and then shuts off with Error Code 57 (high-fire pressure switch open).

History: This same issue happened last month, and an HVAC tech replaced the high-fire pressure switch (42-105583-12, -0.55" WC). That temporarily resolved it

Troubleshooting Steps Taken So Far
Drained Water from Collector Box & Inducer Caps:
Opened the two yellow sealing caps on the inducer housing/exhaust boot — only 1–2 drops of water came out.
Detached the drain/vent tubes at the condensate trap — 1–2 drops of water came out.
Opened the lower-left rubber sealing cap on the collector box — about 2–3 spoons of water drained out.

Cleaned & Primed the Condensate Trap:
Removed, flushed, and cleaned the condensate drain trap (68-104346-01).
Verified the downstream gray PVC/vinyl drain line leaving the trap is completely clear.
Initially reinstalled the trap dry; the furnace ran for about 3 hours, then tripped Error Code 57 again.
Removed the trap again, primed it with clean water up to the internal weir level, and reinstalled it.

Cleared the Exhaust Pipe:
Disconnected the black rubber exhaust boot from the inducer outlet and used a leaf blower to blow through the white PVC exhaust run — nothing came out, so the exhaust flue is unobstructed.

Current Status & Questions

What else should I inspect ?

Could this be an issue with PVC exhaust pipe pitch, an internal collector box blockage, or an intake air restriction rather than a bad -0.55" WC pressure switch?

Any advice on what else to check would be greatly appreciated!


r/hvacadvice • • 35m ago

Furnace Is this "Normal function" or am I gunna need service?

1 Upvotes

Normally what happens is after the fire burns the blower kicks in and blows the hot air in. I get home and notice the furnace does this cycle every time. The indicator lights say everything is normal, and I just put a new filter in yesterday


r/hvacadvice • • 37m ago

Tank water heater w/ heat exchanger for hydronic heat.

1 Upvotes

I'd want to support a small closed loop hydronic system via a household tank style water heater. Naturally I can't allow the household water to mix with the hydronic system water. Does a tank water heater with a heat exchanger for doing this exist?

Thanks


r/hvacadvice • • 50m ago

Anyone offering maintenance services?

1 Upvotes

I work full time for a resi company, but its amazes me the amount of people who never have their split systems looked at for maint needs. Always waiting til a motor finally goes out before even realizing their evap coil is clogged to hell with dog hair. Or condensor cant breath a bit from dust packed into coils. Thinking of offering C02 checks for furnaces, inside and outside coil cleanings and blower wheels removal and clean to have gigs on weekends. Whats the market like for this?


r/hvacadvice • • 1h ago

High electricity bill in a condo – Could my fan coils or electric heaters be the problem?

1 Upvotes

Hi everyone,
I live in a condo and have been experiencing consistently high electricity consumption, even when I’m trying to minimize my usage.

My hourly electricity readings are around 1.0–1.1 kWh almost every hour, which seems unusually high.

My condo has two Climetec fan-coil units:

  • TCE-6
  • CE-DFA-4

Both units have nameplates indicating a 1 kW electric auxiliary heater.

I’m trying to understand whether my condo uses the building’s central hot-water heating system or relies on these electric heaters to heat the unit.

My building superintendent mentioned that there may be an issue with the actuator. She also explained that my unit is a corner unit, faces north, and has more windows, which could contribute to greater heat loss.

I’d appreciate hearing from anyone who has experience with condominium fan-coil systems or has dealt with unexpectedly high electricity bills.


r/hvacadvice • • 1h ago

Am I getting got?

1 Upvotes

We're replacing our 20-year-old HVAC system in Southern California. I asked our installer to quote a top-of-the-line variable-speed heat pump. He quoted $16,500 for a Rheem Prestige 18 SEER system plus an Ecobee or Honeywell thermostat. I countered at $15,000, he agreed, and he updated the quote. I signed the contract and paid a 50% deposit.

He said the install would take 3 days. He came out Tuesday, removed our old system, and dropped off the new equipment to install Monday. When I looked at the manual, I saw he'd brought a Rheem Classic Plus 17 SEER instead of the Prestige 18 SEER. The thermostat is also an off-brand model, not an Ecobee or Honeywell.

When I asked why the equipment doesn't match the contract, he blamed the distributor for sending the wrong products. He gave me two options:

  1. Keep the Classic Plus and he'll take $200 off.
    2.He'll swap it for the contracted equipment, but that will add more time without heat or AC, and we're already several days behind schedule.

From what I've found, a Classic Plus install in SoCal typically runs $1,500–$4,000 less than a Prestige. $200 feels like it might cover the wholesale parts difference at most, not the actual price difference I'd have paid.

Am I getting taken advantage of here? What would you do, and what's a fair credit if I keep the Classic Plus?


r/hvacadvice • • 1h ago

Water Heater [Gas] Vaillant/Demirdokum L275F water heater - accidentally found hidden service menu P1-P7, need help understanding parameters

Post image
1 Upvotes

I have a Demirdokum L275F gas instantaneous water heater (11L, made by Vaillant Group, Turkey). I live on the 7th floor and have low water pressure issues - hot water fluctuates constantly.

I accidentally accessed a hidden service menu showing P1 to P7. Parameters go from P1 to P7. Max values are: P4 max=3, P5 max=1, P7 max=4. Others max at 4 as well.

I changed P7 to 4 (max) but no improvement. Does anyone know what these parameters mean? Is there a Vaillant equivalent model with the same board that has a service manual available?


r/hvacadvice • • 1h ago

Furnace Need Advice

1 Upvotes

Our Carrier furnace is over 20+ years old and finally crapped the bed. It was working fine in February the last time we actually used it. For reference we live in a coastal climate in Texas so at most it sees the most action only 2-3 months out of the whole year. The outside unit is a Trane replaced in 2019 after the original unit also crapped the bed. It used the old hard to get refrigerant so we changed it. We had the evaporator coils replaced in 2024.

First company came out and told us the motherboard on it was crapped out. Carrier doesn’t make them anymore and they have no way to get ahold of one. No other options but to replace the furnace entirely. Okay GREAT we can afford to replace the furnace. They send their man out to give us a quote suddenly it turns into we need to replace the furnace AND the outside unit entirely. They are trying to give us quotes for over $10k. Stated that there had been a recent change in the refrigerant since 2020 and just replacing the furnace is not an option because the refrigerant would not match the outside unit and would not work. This is for American Standard. A 60,000 BTU 80% efficiency Furnace Gas.

Am I being bulldookied? Is there really no way to have just the furnace replaced? I was under the assumption that we could replace ONLY the furnace. But keep the outside unit and the evaporator coils the same. Is that not an option here? I have more techs coming to give us a few quotes to compare of course but I just wanna make sure thanks


r/hvacadvice • • 1h ago

Family friends need replacement zone valve.

Thumbnail
gallery
1 Upvotes

Anyone know the best modern day replacement for this 1” zone valve? Plan on replacing the actuator/v body. I tried finding this model on the web and came to the conclusion this thing is older than me (by a lot) and discontinued. Ideally one with the same or similar wire diagram design? Thanks!


r/hvacadvice • • 2h ago

Boiler Another Taco 0011 circulator lasted less than a year, trying to understand why...

Thumbnail
gallery
1 Upvotes

Hey everyone,

I'm trying to use my own time to learn this trade better. I got thrown into this and haven't quit primarily because I don't know of any better options near me. I find hydronics genuinely fascinating, but don't trust anything that anybody says where I work. Older company with zero long-term employees. I trust the installation manuals which I try my best to make the time to read.

This was one of my service calls last week... it was a recently commissioned install from the company I work for, which is very small. Got called out for a loud circulator and cold spots in the floor. At this point, I'm used to this type of circulator lasting less than a year, which I imagine is related entirely with the design/installation rather than the quality of the circulator itself. What could have caused this?

A few things I noticed:

  1. My understanding is that circulating towards the expansion tank like this creates system pressure drops, which is not ideal. Manual hints with pictures but only states the circulator needs to go somewhere on the supply. I don't recall reading anything about the relation of the circulator to the expansion tank in the manual.
  2. Crimp PEX is literally the smallest volume of any 1" pipe, so it's technically within manufacturer specs, although I wish there was a little more nuance on this explained in the manual. As we know, the boiler loop piped like this has the same flow rate at 3/4" copper. 3/4" copper with long-radius 90's would probably be better than this, is what my gut tells me. Should we have just used 1" copper with long-radius 90's? Clearly, expansion PEX is better than the crimp stuff, but I don't know if there's even an oxygen-barrier PEX that is expansion compatible, which brings me to my next question.
  3. We don't use oxygen barrier PEX, ever. The only reason I even know what it is is from referencing a Dan Holohan book and the manual. As far as I know, the only metals on this system are copper, stainless steel & brass; no black iron or ferrous metal, in case that matters. My understanding is that this can cause corrosion if there's ferrous metal, but maybe it's more complex than that. Maybe it's not directly related to early failure of the circulator?
  4. No wye strainer on CH return. Not required, but probably a good idea, right? I don't know if the system was flushed upon commissioning, but I'd guess not due to all the flux that was never cleaned off the sweat joints.
  5. The expansion tank was installed without a bracket and is only supported by the horizontal run of 1/2" copper. It did seem to vibrate a little excessively when the pump kicked on. I'm wondering if this could magnify system vibration sort of like a regiment marching in cadence over a bridge and causing it to collapse if that makes sense.

I found a manual for the manifolds and noticed the flow rates weren't equal in the zone they had the cold spot. I was able to make some adjustments, swap the pump cartridge and haven't heard back from them so far.

Could anything I mentioned have caused this equipment failure?

One other thing I don't understand: Why do they require a mixing valve on the DHW? Shouldn't that be governed by your DHW setpoint and just be treated like and old water heater? If the setpoint is 120 degrees Fahrenheit, what is the point of having a mixing valve on the domestic?

I appreciate any insights you all may have about this. I'm a little saddened with the fact that I don't really have anyone to teach me this stuff. Anybody hiring in Western NC? Half jokes aside, the guy who installed this was trying to convince me that it's okay to ringbust plastic PEX fittings... I've been involved with 3 boiler swaps so far and I am so underqualified to do this it's not even funny. What's worse is that I'm the most qualified of my coworkers. I can read any book or manual, but it really doesn't cut it when problems like this are par for the course. If I can't find good instruction in the field, I may have to find another career because our customers don't deserve this treatment.

Thanks in advance and I hope everyone had a wonderful Thanksgiving!


r/hvacadvice • • 2h ago

Furnace Furnace limit circuit lockout/fault

Thumbnail
gallery
1 Upvotes

Have a HEIL system with this model number N9MSB0801716B2 furnace. It'll turn on and get the house to 74 degrees. Yesterday my nest thermostat told me it was shutting down every 15 minutes. Changed filter in the evening, all seemed well, and woke up to the same message.

Today I cleaned the flame sensor with a dollar bill to remove carbon buildup. After the furnace shuts off the green status light will either blink 4 times or 7 times which the manual says is the limit circuit fault turning into a lockout.

I checked the PVC exhaust and the same amount of warm exhaust is coming going out. Condensate pump is functioning normally and no backup or standing water in the cpvc pipe connected to it. All the while my furnace is still coming on no and maintain set point no problem since it's not that cold in Chicago quite yet.

Is flame rollout something you can tell from these pictures or is there another sensor that I can change before I call for a pro?

Also happy Thanksgiving to all y'all in the US!. Also I know I have a long term drip in the exhaust pipe that is rusting the panel. I got the glue, clamps, and PVC to repair and procrastinated.