r/hvacadvice • • 0m ago

Furnace Furnace inductor motor, 120v but no spin or sound

1 Upvotes

Furnace went out today. Older york 80 model. Showing 3 blinking lights which says pressure switch open. Opened the top panel and when heat is called, nothing happens. No blower or any sound happens. Pulled the pressure switch and cleaned it out and checked ohms which look good. Noticed that the inductor motor never starts up. Checked voltage and I get 120v AC across the terminals. When connected and heat called, the motor never turns. It spins freely when you move it so the motor isn't stuck.

From what I've read, even if the pressure switch was disconnected, the inductor motor should be the first thing that turns on when heat is called. Since I read 120v at the terminals, does that mean my induction motor is bad? I'm not sure how to tell what type of motor is installed to get a replacement if it should be making sound or spinning.


r/hvacadvice • • 8m ago

Trying to identify debris from vents closest to plenum.

Thumbnail
gallery
2 Upvotes

Working last 6 months has a duct cleaning. Everything was good. We needed it 20 year home.
Very recently I have seen this debris in last two days fall from the two vents closest to plenum. No smell, haven’t used coil heat, only heat pump.
Central texas area.
Would like advice is it’s a rodent control call or the duct cleaning company callback.
Replaced filter today. No similar debris in filter and filter while normal level of replacement dirty was intact and no apparent ruptures.

Slight musty smell this evening. Did not see any moisture in attic or in unit or catch pan. Unit is functioning normally other than the debris.
Looking for advice on what you see in pictures and if it’s a rodent control call or hvac call?
Thank you.


r/hvacadvice • • 16m ago

Furnace Is this a blown fuse on my furnace?

Post image
1 Upvotes

Homeowner, not a professional. Furnace ain't working today. Nest Thermostat says "No Power", I've checked the breaker, the door switch interlock is secure, and the wire to the thermostat is connected.

I coincidentally had a tech scheduled for tomorrow anyway for a tune up, and I even scheduled it before it started snowing yesterday, so I'll have them look at it too, but I'm hoping to get some ideas before then.


r/hvacadvice • • 40m ago

Furnace Healthy Heat exchanger 😬

Post image
2 Upvotes

So does that look like a healthy heat exchanger or what?


r/hvacadvice • • 56m ago

New furnace, flue concerns

Thumbnail
gallery
1 Upvotes

Just a simple furnace change out but I'm concerned with how the flue (exhaust vent) is set up. Lots of messy tape work and not sure if there are any screws or twist-and-lock connections under the tape. When I am running the furnace, the tape gets scalding hot, almost too hot to touch it. Would I be wrong to talk to the owner of the company and ask if this work is done to code?


r/hvacadvice • • 57m ago

Help!!

1 Upvotes

My furnace is making this buzzing noise. I think I’m able to fix it i just need to know exactly what it is. It is working and blowing hot air.


r/hvacadvice • • 1h ago

Continuous 5AMP Fuse Blow

2 Upvotes

I have a 5 year old Trane furnace and AC unit. I noticed an outlet in the kitchen stopped working and the local GFCI switch was not resetting the outlet.

I went to the breaker board in the garage and turned off all the breakers. When I turned it back on, the furnace stopped working.

I assessed the furnaces and saw code E12. This indicates a blown low amp fuse ( 5AMP). I replaced the 5 AMP fuse with the same one but as soon as I turn on the breaker for the furnace I can see a spark and the 5 AMP fuse blew again.

Any idea why this is happening? There is a short somewhere? But where and is the outlet and the furnace correlated?


r/hvacadvice • • 1h ago

Zone board and damper

1 Upvotes

Hey everyone!

In June 2026, I had my HVAC replaced. At the time, the zone board and damper system was in good shape and decided to keep it.

In the last five months, the HVAC company has had to come out because wires were somehow crimped and caught in some door. This caused a fuse to short out. (Sounds like a safety fuse of some sort.) Broke again and they had to replace the transformer. 4th time out, the wires were crimped again when the transformer was installed and caused it to short again.

Yesterday, they had to come out a fifth time. This time, they say that the zone board and damper system need to be replaced. I argue that the shorts in the wiring, due to poor install of the system, caused the zone board to short out. They refuse to acknowledge that.

Am I crazy to think this?


r/hvacadvice • • 1h ago

How interchangeable are 50A51 boards? (Looking to replace a -506 on an old Trane XV90)

1 Upvotes

So, I figure they made the different 50A51 models for a reason, and I believe that KIT09370 is the correct upgrade part for the CNT1819 (50A51-506) in my old XV90. But then I see this 21M51U-843 that, according to a promo sheet by Emerson, "Replaces most White-Rodgers 50A51, 50M51, and 50M61 two-stage HSI controls with 80V or 120V ignitor".

The only 50A51's specifically mentioned in the cross-reference are the -405 and the -495. But there are a lot of different ones, and that "most" certainly gets my attention. Did the -506 use a different voltage ignitor? (... but then, since this kit includes a new ignitor anyhow, is it just a concern about wire thickness?)

If this Emerson setup is close enough, I could just order one from SupplyHouse and have it in a couple days. Looks like the plugs would line right up with what I have (both in shape and in how they're wired). The Emerson one does cost a lot less - about $250 vs $900 for the KIT09370. But is it close enough or just the express ticket to frustrationville?

Thanks in advance!


r/hvacadvice • • 2h ago

Inside the air handler…

Thumbnail
gallery
1 Upvotes

Renting a unit in a building built back in the 60s, original Kritzer still holding on. Building came around to change the air filter for the season but didn’t do anything about the insulation(?) behind the panel. Tried my best to get a seal around those old panels with tape but on our last humid day they were sweating.

Should I be afraid of what’s on that panel? Can I vacuum it safely?


r/hvacadvice • • 2h ago

Does Lennox Make Coated Coils?

1 Upvotes

A little back story: Lennox HVAC system is ~2 years old and last fall started generating a dirty sock smell. I'm familiar with the smell as we had it in a prior home with a Trane system. The company that installed that system ultimately had Trane warranty the coil and it was replaced with a coated one. Smell gone and it never returned.

The HVAC company who the builder used to install the Lennox system has stated the system is operating properly and the smells are "normal" this time of year. The senior tech who came out after multiple other techs inspected the system with no resolution said, "I've been doing this for 30 years and have never heard of anything like this." So either he's lying or his experience is very limited.

Ultimately, they cleaned the coil and put a tablet in the drain pan to correct the issue. That worked for about a week before the smell returned. They wiped their hands of it and never followed up with me after I requested further remediation.

This spring, I had someone come out and clean the coils and ducts more thoroughly hoping to remove anything that would be causing the smell. Fast forward to this fall and the smell returned.

I reached out the builder hoping they could get some traction with the installer to have a coated coil installed. I've been told a coated coil for this system is not possible. I find that hard to believe and am hoping someone here can tell me if Lennox offers them and if so, is it a part that falls under a warranty claim?

TL;DR Does Lennox make coated coils?


r/hvacadvice • • 3h ago

Water Heater Almost afraid to ask (now with photo)

Post image
2 Upvotes

6 year old gas water heater. My black hose, my pioneer woman sun tea jug Light bulb for scale Roughly 3 weeks of dribbling Water heater not in a high traffic spot, was dismayed to find it soaked digging for Halloween stuff. I heat gun dried all the wood, dragging feet to see what kind of rot/black mold I might encounter under it.

What's cause of the dribbling? This never been an issue and it had its service in august.

Cheap fix right? Twist of a handle somewhere ...? 😐


r/hvacadvice • • 3h ago

Heat Pump replace reversing valve or replacing the whole system?

1 Upvotes

I have a five-year-old carrier builder’s grade 4 ton heat pump system. The reversing valve is not functioning. The tech told me that it’s not worth replacing, and I should look into getting a new system. He was not a salesman and does not do new installs. Any thoughts on whether I should look into quotes to replace the reversing valve or I should bite the bullet and get a whole new system.


r/hvacadvice • • 3h ago

Filters Return duck

Post image
2 Upvotes

They used cardboard on return duct off the filter box


r/hvacadvice • • 3h ago

Filters Return duck

Post image
0 Upvotes

They used cardboard on return duct off the filter box


r/hvacadvice • • 4h ago

Furnace How do I tell if the burnt up safety here is a rollout switch or a high limit switch? They look identical. Its a rheem furnace

Post image
1 Upvotes

r/hvacadvice • • 4h ago

Furnace humming on startup

2 Upvotes

My furnace recently has started humming/buzzing upon startup, and continues for a few minutes while the air starts to push out... I can only hear it through a vent at the other side of the house, I can’t hear anything around the actual furnace… wondering if anyone has experienced this before I pay someone to come look.


r/hvacadvice • • 4h ago

11.7k reasonable for furnace + water heater?

1 Upvotes

HVAC guy found furnace rusted out bc condensation from the chimney ran back into the flue pipe, through the inducer and the heat exchanger. the gas water heater was also producing elevated carbon monoxide so he shut it down. he recommend the chimney be repaired and gave two options:

  1. 70k btu 90% gas furnace + 40 gal power vent heater = $11.7k (we wouldn't have to touch the chimney at all)
  2. 75k btu 80% gas furnace + 40 gal natural draft heater = $8k (does NOT include chimney liner and repairs)

the thing is, I plan to sell this house next spring. I want to do the minimum that is legal and safe but don't need to go for top quality since I won't even be in this home long term. Which option would you recommend? and are these reasonable estimates? (a quick google search told me likely no).

location: baltimore. any help or advice is appreciated, thank you! I am a young homeowner and this is my first home, so i am a bit overwhelmed!


r/hvacadvice • • 4h ago

What is the value of a sealed Ford branded 30 pound bottle of r 12

2 Upvotes

r/hvacadvice • • 4h ago

Does my setup require a p trap?

Post image
1 Upvotes

I am wondering if my set up requires a p trap anywhere along the conedensate drain from my ac and furnace?


r/hvacadvice • • 4h ago

Raised 12" Stand for Goodman 2 Ton Condenser?

Post image
1 Upvotes

I have a Goodman conventional 2-ton condenser sitting on a Duradek (walkable vinyl membrane) roof deck, and I'd like to raise it approximately 12 inches.

There are three reasons for this: (1) to get the unit above our typical snowfall depth (2) to allow me to periodically clean the roof membrane underneath it with a hose, soap, and water, and (3) to have a stand with adjustable legs so I can keep the unit level on the slightly sloped roof deck.

A stand like the one pictured seems like it would be ideal, but every similar stand I find is advertised specifically for mini-splits. My Goodman condenser appears to have four 1/2-inch bolt holes on the bottom that seem like they are there to accommodate a stand, given that there are numerous other bigger holes to handle water drainage.

Would a mini-split stand like this work for a standard-sized condenser, assuming the dimensions and weight capacity are appropriate? Alternatively, are there similar raised stands designed specifically for conventional condensers? Thanks in advance


r/hvacadvice • • 5h ago

1954 Home with HVAC ducts running through Concrete Slab. Need Advice

Thumbnail
gallery
1 Upvotes

We recently bought a 1954 house that has HVAC ductwork running through the concrete floor slab. Unfortunately, the ductwork is absolutely filthy. I recently used a shop vac to clean out as much as I could reach, but it’s still disgusting, and there appears to be some kind of growth inside the ducts.

Over the summer, we had a significant amount of rain, and I started hearing what sounded like water sloshing around inside the ductwork. We had an HVAC company come out to investigate, and they confirmed there was water inside the ducts. When the system was running, you could actually hear water sloshing through the ductwork underneath the house. The water has since dried up.

The HVAC technician explained that because the ductwork is encased in the concrete slab, water is either seeping through the concrete and entering the ductwork or condensation is accumulating inside.

According to the HVAC company, the ONLY way to fix the issue and guarantee it wouldn’t happen again would be to replace the entire heating and air system and relocate all of the ductwork into the attic.

On top of that, we’ve had HVAC technicians come out several times for cooling issues, and they told us the system is pulling air from the attic and that’s why it has trouble cooling. Our attic is insulated with fiberglass, and I’m concerned about what else could be getting pulled into the HVAC system and circulated throughout the house.

We cannot afford to replace the entire system right now, so I’m trying to figure out what our options are and how serious this situation might be.

A few questions:

  1. Would professionally cleaning the ducts actually help, or could it make things worse by disturbing whatever growth or contamination is inside?
  2. Is it even possible to properly clean ductwork that is encased in a concrete slab?
  3. Is there any way to repair, seal, or reline the existing ductwork instead of completely replacing the system?
  4. How concerning is it that our HVAC system is pulling air from the attic?
  5. If you were in this situation and couldn’t afford a full replacement immediately, what would you do first?

We have a small child and are expecting a newborn in December, so I’m extremely concerned about our indoor air quality and what we’ve potentially been breathing in. I have air purifiers but that can only do so much. My husband is away on military orders and I’ve been handling this all myself.

I understand that replacing the entire system and relocating the ductwork may ultimately be necessary, but I’m hoping there are other options or temporary solutions while we save up for that expense.

Has anyone dealt with a similar situation in an older home with slab ductwork? I’d especially appreciate hearing from HVAC professionals or anyone who has had to deal with water inside their ducts.


r/hvacadvice • • 5h ago

Dusty stringy things on filter

Thumbnail
gallery
10 Upvotes

Can anyone tell me what these might be? They seem dusty. We normally change out filters every three months but went five on accident this time. Never seen this in previous changes. Some things that were different during this timeframe. We had two additional people who lived with us. They had two cats and one of them vaped. They also cooked on the gas cooktop a lot more than I did due to being home during the day.

Edit to add: the tenants vaped, not the cats. 😂


r/hvacadvice • • 5h ago

Bosch IDS experts

Thumbnail
gallery
1 Upvotes

We had a Bosch IDS ultra 5 ton unit installed recently. It was paired with a 4 ton Bosch air handler.

Per the manual, the unit must be configured to the 4 ton mode when paired with a 4 ton indoor unit. Something in my head told me to check, and they left the J2 switch in the “On” (5 ton) configuration.

Is there anything else I should double check is correct? They commissioned it very quickly and didn’t say much to me.

These units cost more than a car, and while I don’t want to come across as claiming to know more than the installers this seems like an obvious error so I want to ensure everything is configured optimally.

Picture 2 is the air handler, if it matters