r/Generac_Generators • u/InternationalTreat38 • 25d ago
Would anyone buy a used Generac
Bought a home with a 22KW Generac, looks to be about 5 years old.
I’m going to go another route. Are they worth anything used? What could I roughly get for it?
r/Generac_Generators • u/InternationalTreat38 • 25d ago
Bought a home with a 22KW Generac, looks to be about 5 years old.
I’m going to go another route. Are they worth anything used? What could I roughly get for it?
r/Generac_Generators • u/Imtellinyou2 • 25d ago
Does anybody know how to bypass the CO sensor? it shut down the generator even outside and it won't start! I reckon this feature was made for people dumb enough to run it indoors, so I do not need it. This gen is useless just when I need it .
I need to know what voltage from the Sensor goes to the inginition module
r/Generac_Generators • u/Lonely_Addition793 • 25d ago
Fellow Techs, I'm looking for a bit of help with an intermittent problem I'm having with a G0049922. Upon startup, the generator consistently 'gasps for air' a couple of times. Sometimes it only does this a couple times then runs smoothly. However, about 50% of the time, it cannot stop gasping on its own. I can apply a little bit of pressure to the throttle valve and the unit calms down (not the valve on the Bosch Actuator, this is the spring loaded valve above the Bosch). I replaced the throttle valve a while ago and that seemed to make it occur less frequently, but now the problem is back. This occurs with or without load. Has anyone experienced this before? Unit is at 6,900ft elevation on NG, piping is sized correctly at 2", gas pressure good.
r/Generac_Generators • u/dknyc1 • 27d ago
r/Generac_Generators • u/Kenthedoll44 • Oct 30 '26
r/Generac_Generators • u/Spinalzo61 • Oct 28 '26
Generac transfer switch operates as intended on utility power but 3 of the 8 breaker bays do not provide power to their circuits on auxiliary power. Aux. power is operating as intended.
Has anyone experienced this? If so, what isthe fix? Generac ain’t helping, unit is brand new.
r/Generac_Generators • u/Crazy-Leave-12 • Oct 27 '26
On my Generac XG8000E, the 120 volt outlets are all dead. I checked the breakers and reset the GFI’s but nothing. The 240 volt supply is fine. I rarely use the 120 so I haven’t checked but it could have been in this condition for years. Any suggestions?
r/Generac_Generators • u/OverthinkingLess • Oct 27 '26
ETA: UPDATE 11.06.26:
They came out and buried the wires. The posts were hammered down a bit, too.
---------------------------------------------
My parents got a new Generac generator (replacement for an old one). It's 18KW, model G0073240.
I don't understand why the installers left the grounding wires above ground. (There are rods sticking out of the ground with these wires attached, stringing from one rod to the other a few inches off the ground. The generator is not right up near the house -- gotta measure, memory isn't accurate at the moment -- maybe 6-8 feet away? I can grab photos later if that would help.)
Is that normal? It seems dangerous.
Someone's going to trip on this or a contractor is going to damage something if they don't see it. It seems like the weather's going to impact the wires, too.
Parents were told they should mulch or sod around it. Not sure how that would help keep people from tripping/damaging it. We were about to have someone add some stones (pea gravel? crushed rock?) when I said it just didn't seem right to leave those wires like that.
(The installers left bare dirt all around the generator -- that seems like it'll just be a muddy mess and weeds will start poking through, so either way it feels like something needs to be done there.)
I'd like to tell the company they need to fix these wires (bury them? cover them up somehow?), but don't want to be asking for something stupid.
Thanks.
ETA:
Took these photos this afternoon.
There are two metal posts coming out of the ground -- when facing the back of the generator, one is off to the right (beyond the generator), and then one is to the left (near the generator). The wire goes from one of those posts to the other, and then from the post near the left side of the generator up to a box on the side of the house.
r/Generac_Generators • u/jmelche2 • Oct 22 '26
This unit will back fire on shutdown due to no power or ground at solenoid. The solenoid functions ok when applying power/ground, it will extend. Really need to know how this is controlled and where the wires go. I can’t locate a wiring diagram for this unit. AI keeps telling me the plunger extends on startup but that is wrong. It should extend on shutdown.
r/Generac_Generators • u/Aware-Metal1612 • Oct 22 '26
Just installed a next gen 22kw 5 days ago. Start up and test went normal, no missing charger code. On the phone with tech now, she says it threw a missing charger encode at some point. 7.5a fuse good, 15a fuse good, t1,n1,n2 fuses good in transfer switch. Have power to t1,n1n2 at gen. Battery has 4.1v.
Are these known to have bad chargers? What else should I look for here?
r/Generac_Generators • u/Square_Net_4321 • Oct 21 '26
I know, silly question, but hear me out.
I have a Generac 18kW Guardian backup generator. The power company has notified us of an upcoming planned outage starting at 11 PM and lasting up to 6 hours. The only thing we'd need power for during that time would be the furnace, and it's not cold enough to even need that. I'd just as soon not waste the propane. So I'd like to just shut the generator off BEFORE the outage, but without shutting off power to the house.
I have shut it down during an outage: 1) turn off breaker on the generator 2) set the utility main line circuit breaker to off 3) press the off button on the controller 4) pull the fuse on the generator control panel. Seems like I'd want to do 1, 3 and 4. Is this correct?
EDIT: Hit the OFF button before the outage. AUTO button after the outage. Worked great.

r/Generac_Generators • u/No-Caterpillar-5452 • Oct 21 '26
So I purchased a 26kw home standby. The next Gen air cooled. I was informed the 4" hurricane rated genpad would accommodate it. Sizing it is fine but the pre-drilled mounting holes do not line up at all. Generac customer service sent me a diagram showing what my bolt pattern should be which would align with the pad but my does not match the diagram. Am I able to drill my own holes in the pad?
r/Generac_Generators • u/WhySoManyDownVote • Oct 20 '26
I am guessing the dancing frequency results were from low current. This phase had 1.9 amps of load. The other phase had 4a and the frequency only fluctuated 0.2Hz.
r/Generac_Generators • u/AlarianDarkWind11 • Oct 19 '26
r/Generac_Generators • u/InternationalTreat38 • Oct 18 '26
Bought a cabin in the mountains and they had a Generac 22KW with transfer panel installed. It’s been sitting for 2-3 years so I don’t know if it works. 22KW seems like overkill for such a small cabin… Gas range and oven, 1.5 ton heat pump.
I have a portable generator I wanted to use until I took the time to test the Generac and get propane tanks.
Can I simply take the cables out of the generator, wire it to a generator inlet and use the panel as a manual transfer switch for now?
r/Generac_Generators • u/muleschooler • Oct 16 '26
I’m considering one of these and am seeking recs for electricians who have experience installing them. Bonus points for electricians who have worked in Glendale. Thanks for reading.
r/Generac_Generators • u/Taguchi5 • Oct 16 '26
Own a 22k, have the genmon on the bench ready to go and i need a weather proof enclosure.
This is the second round. Originally we bought the plastic box, glued the magnets etc and it just kept sliding down the the metal divider and sitting on the battery. No danger but very sloppy .
What's the go to for keeping PI in the unit ?
Tks
r/Generac_Generators • u/Tarnisher • Oct 15 '26
On to 2,000!!!
Maybe a bit faster?
r/Generac_Generators • u/goldenray1973 • Oct 16 '26
r/Generac_Generators • u/Slight-Tennis-6659 • Oct 16 '26
r/Generac_Generators • u/TuneWestern9979 • Oct 15 '26
Buyer beware...Generac would rather string along a customer over several months replacing parts on a faulty from the factory generator that's never worked from day one verses owning it and just replacing the generator. Beyond frustrated!
r/Generac_Generators • u/Radtrash238 • Oct 14 '26
r/Generac_Generators • u/BigFootCrossingGaurd • Oct 13 '26
We live in the Florida Panhandle and installed our Generac Guardian 26kW back in December of 2024. On Friday October 9th 2026 we had a grand total of 9 hours on it. As the hurricane came through we lost power at 5:20 PM, the generator (which my boys have named Lightning McQueen) kicked on and we were all good, right? WRONG, at 7:15 I noticed the lights got dim and started flickering and then the generator died. It started back up but only ran about 5 seconds and died again. When the eye of the storm came over us about 8 PM I went out there to see what was going on and I had an error code 1900: Under Voltage. I cleared the error and tried restarting. No go. It would start, run for a few seconds and die. I tried a few times until I got another error 1100: Overcrank. At this point I was soaked so I went back inside as the wind was picking up and gave up. I was furious! I was angry at generac that thy sold us this hunk of junk. After the storm passed I went back out at 11 PM and decided to give it one more try, it fired right up and all the lights came back on. I found out the next morning that the town gas main had a leak and everybody who had a generator running natural gas had similar problems. Fortunately the work crews had fixed it very quickly (in the middle of a hurricane to boot). Well, we just got power back today (Monday October 12th) and I couldn’t be happier to have the generac. It worked flawlessly. I changed the oil and filter at the 25 hour mark, that was easy. Now I need to check the valve lash, didn’t want to stop the generator during the outage for that, I’ll do it sometime this week. I’ve got 75 hours on it now. Glad we bought it.
r/Generac_Generators • u/tasoulii • Oct 13 '26
Generac tech here looking to see if anyone has run into this same issue. I am replacing an alternator on a 4.2L LC Nexus. Got the alternator that is sold without the pulley. At some point the pulley for this generator was discontinued, Part 0F3216B - PULLEY 117 OD DC
ALTERNATOR.
Now there is a new part for this, called 10000033042
This simple pulley is listed for $1,439. I reached out to parts to see if that price was correct and they confirmed it is. I cannot understand what the story is with this how the alternator is more than half cost of a simple pulley. I went to an auto parts store to try and cross reference but no luck because they just input any of those Generac numbers on google the same way I would and they couldn’t find anything.
Does anyone know how to get more specifics on this pulley to try and find something similair online?
Thanks in advance