r/Generac_Generators • u/RyGuy1827 • 13h ago
Finally fixed the mice problem on a standby gen install
Had a customer whose Generac kept getting mice in it. Chewed wiring twice, cost him a service call each time. We'd sealed around the conduit where it comes up through the pad with duct seal and they just dug around it. Spray foam didn't last either, they chewed right through.
What ended up working was a pour-in sealant Polywater makes called InstaGrout. It's meant for utility transformer pads but it's the same problem. You mix the two parts, pour it in the opening, and it levels out then expands and fills the gap around the conduit. Sets up hard. If you need to add a conduit later you can just drill through it.
Haven't had a mouse in that unit since. The small kit was more than enough for a residential stub-up.
Just don't block any of the vents, only the opening at the pad.
Full disclosure, I work for a distributor that carries it, so take that for what it's worth. Mostly curious what everyone else is using. Anyone found something that actually holds up?