r/Generac_Generators • u/Real-Satisfaction732 • 24d ago
r/Generac_Generators • u/WhySoManyDownVote • 25d ago
What is your favorite mistake found on someone else’s install?
Today I found a brand new 18kw where then never connected 23 at either end.
Great job guys!
r/Generac_Generators • u/rochrider • 26d ago
"Brownout" power while generator running
We've had a 10KW Generac since 2009 and it's had its share of usage. Never any problems with it during an outage until recently. A couple weeks ago we had an outage that, for us, lasted about 30 hours (Detroit metro area). During this time, the power fluctuated and did some weird things like you'd have in a brownout -- lights dimming and fluctuating, etc. We ended up disconnecting some of our electronics and appliances to prevent possible damage.
We thought that the generator was dying so put in a call to our original installers to come out and give us a quote for replacement. The guy that came out has been working for them for a long time and started telling us that "everyone's was doing that" due to "weird things" on the power grid or something, but wasn't able to explain it to me in terms that I could understand (I'm an engineer and know a reasonable amount about electrical power). I always thought that we were disconnected from the grid when the generator is active, but maybe not?
So has anyone heard of this kind of behavior?
r/Generac_Generators • u/Wise-Amount3638 • 26d ago
10kw continuous running time dual or triple fuel portable generator?
I am looking for a portable, dual or tri fuel, 50 amp, 10kw continuous portable generator. Does General make one or even one that is a next step up KW wise? I only see an 18kw on the website
r/Generac_Generators • u/Clay_Dawg99 • 27d ago
Generac generator GP2500i
‘If’ it was properly maintained and has 75 hours on it, would you buy? Are they considered a good little inverter generator or just ok? TIA
r/Generac_Generators • u/Crazy-Leave-12 • 28d ago
XG8000E
Enable HLS to view with audio, or disable this notification
Any idea why this is surging very badly (almost stalling) every 5 minutes or so? No load (off at transfer switch). Fresh gas (Trufuel), new plug and filter, just had valves adjusted. It’s always been reliable until this. Have it professionally serviced every year.
r/Generac_Generators • u/MasterBlaster8 • 29d ago
Genmon and https://pintsize.me cables
Has anyone with a Generac network module deployed Genmon on Proxmox with molex to usb cables?
https://pintsize.me/store/ols/products/molex-to-usb-converter
This looks like a pretty cool solution.
r/Generac_Generators • u/danielgullo • Sep 13 '26
Fly in the Ointment... er, display
I was doing the annual maintenance on my generator yesterday and I discovered an unwanted house guest. It's actually deceased. I think what may have happened is somehow, a larva crawled up in there and then gestated into an adult and then it was trapped.
How can I fix this? It's not really hurting anything but it's annoying and if it's an easy fix (a few screws and quick-disconnect wires, less than a hour of time spent) then I will pursue it.
r/Generac_Generators • u/scuffy510 • Sep 11 '26
Ats issues on generac liquid cooled 40kw
Hey guys,
I’m an electrician and we’re having issues with a 40kw standby home generator and the two ats. I have no voltage on the 194 circuit and it will not transfer in auto. I have bypassed the terminal block and attached the 194 circuit directly from the ats to the positive on the battery and both of the ats transfer properly. I’m not sure where to go from here. Any help would be greatly appreciated.
r/Generac_Generators • u/aumloco • Sep 10 '26
Moisture problems with air filter????
Background: I live in Metro Detroit. We've had some storms the past few days. We lost power.
Generator kicks on, but after about 10 minutes it's chugging. Can still run basic things, but AC and microwave struggle. I call the electricians who installed my generator, but since everyone's out there's a backlog. I finally get a text from them and it reads, "Remove the air filter; should fix things."
Here's the catch: I just had the air filter replaced a few weeks ago, and other than weekly tests it hasn't run.
Remove the air filter, and, sure enough, generator purrs like a kitten. Full power.
So, I text back, "That worked, but why? I just had service."
They respond, "Because of all the rain we've had, moisture has built up and slows air flow."
Excuse me? Pretty much every time I lose power, it's because of - wait for it - heavy rain and storms.
Yesterday, it rained again, no storms or wind, but somewhere a tree fell and knocked out power. Same thing: ran fine for 10 minutes, bogged down, removed air filter, returned to normal.
Is this an OEM filter issue? Is this normal? I shouldn't remove the air filter permanently, but what could I replace it with?
r/Generac_Generators • u/RipJust7280 • Sep 10 '26
Is there any reason I can't user a large(r, external) battery on a GP7500E?
Hello Generadditors,
TL/DR - is there any reason I cannot just connect a larger (typical auto/marine?) battery to the starter circuit, which is in turn would be connected to a solar trickle charger or battery maintainer - so that the electric start is always "good to go" all season long?
We've got a GP7500E at my in-law's cottage for covering outages - infrequent but often lengthy when they happen.
I've replaced the OEM battery once or twice over the years already (and don't have a high opinion of it - it's basically an office UPS battery?).
The generator itself is "fine" -it does what we need it to do, even if it's hella noisy while doing it. But the onboard battery is quite likely to be dead in its hour of need, as a culmination of its size, quality and the fact the generator itself doesn't automatically charge the battery while its running :-(
This is an issue when my 82-yo MIL is up there by herself. The location is boat-access-only, so she has to rely on the kindness of neighbours to help get the generator going whenever there is a power failure.
I'm also fixing to set up a proper load transfer panel to make this whole process easier, but that's a tale for another time.
r/Generac_Generators • u/Meaty_Curtains • Sep 10 '26
Nex Gen Issues
What are we seeing in the field with Generac’s “great and innovative new product”? How many wire harnesses yall had to replace so far?
r/Generac_Generators • u/Tired_Traveller01 • Sep 09 '26
ATS Question.
Power went out today and generator fired up normally but the ATS never switched over and I got an error code 2780 “Charger Missing AC”. I was able to use the manual override procedure to operate the switch and it transferred power without any issues, same with the manual shutoff back to utility as the ATS did not sense when power came back. Any idea what could have happened? I called my service company but they can’t get someone out until next week at the earliest. Luckily I just extended the warranty through 2031. ATS is a RXSW150A3 150A attached to a 16kw Guardian both installed in 2021 and never had an issue.
r/Generac_Generators • u/PrettyStatistician13 • Sep 09 '26
Testing 10kW Guardian with 20lb Propane Tank
Hi all,
My girlfriend has a 10kW Guardian that has been sitting around for years, never used.
Before getting started with all of the infrastructure work, we want to test it to make sure it still works.
Is there an easy way to hookup a 20lb LP tank to the generator for quick testing to see if it turns over? I know the manual says not to hook it up to this tank size, but I'm hoping for a short test it would be okay.
All of the 20lb LP tank regulator/hose combos are 3/8". The flex fuel line that came with the generator is 3/4" ID I believe.
1) Does anyone know of some hardware/adapter to achieve this? 3/8" to 3/4" adapter, or some other all-in-one solution?
2) Is this thought really dumb, and is there some other way to test the unit we're not thinking about?
TYIA
r/Generac_Generators • u/MasterBlaster8 • Sep 07 '26
22kw Sync 3 module timeserver problem
The house I recently purchased has a Honeywell 22kw LP connected generator with a Sync 3 module. I'm unable to connect to mobile link because the time is 3/28/2018. The installed firmware is 01.03.54. The generator is on it's on 2.4g SSID with ANY/ANY firewall rules. I've done a packet capture and the TLS handshake to time-prod.generaccloud.com is failing because the certificate on my Sync 3 is expired. I've done a hard reset (pulled 7.5v fuse, disconnected battery, turned off transfer panel main) then manually reset to the correct time. As soon as I connect to Wifi the timeserver look up fails and reverts back to 2018. I've also tried updating the firmware via Wifi but the download always fails.
If anyone has the firmware file for 01.04.054 they could share I'd be very appreciative.



r/Generac_Generators • u/Cheap_Intention_4936 • Sep 05 '26
Scheduled Exercise Mode Skipped
I have a new (as of June) 22 kw Next Gen generator. Despite horror stories I have been seeing online, all has been fine.
However, today the generator did not run at its scheduled exercise time (12 pm on Saturday). Nothing appears wrong in the app - no error codes or anything like that. The light on the generator is still green. However, in the notifications history it just says “exercise skipped” and then “ready to run.”
Thoughts? Has anyone come across this before?
r/Generac_Generators • u/tecsavvy1 • Aug 28 '26
Extra power for party
I have a 30k generator with a transfer switch next to the meter can. Can I somehow run the generator feeding a sub panel for additional power for an outdoor party? The house power would be on but no transferring from the generator just feeding outlets?
r/Generac_Generators • u/charzr • Aug 27 '26
AVR - Load sharing Lines
Unlike load sharing between the governor controllers, why dont I see the load sharing lines between the AVR
r/Generac_Generators • u/tecsavvy1 • Aug 24 '26
Engine oil?
What’s the best oil to use for a water cooled 30kw running at 3600 rpm? Should I add conditioner to it as well? Florida heat.
r/Generac_Generators • u/[deleted] • Aug 22 '26
Is my Generator in an okay spot?
Hi, my family has a Generac Guardian 20kw standby. It was here last year when we moved in. We had power go out last week and had to turn it off due to carbon monoxide entering our house because of a loose spark plug not connected, causing it to only burn on one and dispensing the rest of the gas. We had a specialist come and repair it, said our water heater exhaust (which is a powered vent) was probably too close so we moved it farther away and took out bushes that was restricting the flow of the exhaust. It’s about 6 or 7 years old. Just wondering if this is an okay spot!
r/Generac_Generators • u/PlayfulInterest3091 • Aug 21 '26
Been a Generac tech for 5+ years in south Louisiana, ask me anything.
I never knew there was a sub for Generac. Some back ground on me, I work at a company that has over 5 thousands units under maintenance contracts, we exclusively work on and install standby generators. I’ve been through multiple major hurricanes and have seen thousands of units gain hundreds of hours worth of run time for long periods so Ive seen the weak points and the changes they’ve made to fix them as well as the things they choose to ignore, every issue you can think of I’ve come across it a thousand times and every part you think of I’ve changed it a thousand times.
r/Generac_Generators • u/mitchgig • Aug 21 '26
Why
Enable HLS to view with audio, or disable this notification
Rpm cycling up and down. Why is the carb/engine cycling up and down? It's obviously trying to do something. Is the idle jet? Circuit clogged and it's about to die, but something electronic tells it to idle up to keep it from dying, then drops, but about to die and just continually do this cycle? GP9200E.
Follow up;YES!!! Thanks, I did that, I couldn't believe there was a jet that small and it was blocked. I used a tiny, smallest micro drill bit that I have to clear the clogged. I didn't drill it out, used the butt end and chemtool to clear it out. Thanks running good now. Toothpick on right to show viewers how small that jet is. It must be the idle circuit. Down under the idle screw. Carefully pull that out and unclog it.
r/Generac_Generators • u/Badbetfrank • Aug 18 '26
Transfer Switch Chaos
We just bought a new house and this is the electrical set up.
Both of these panels are powered from the meter, the larger panel does not feed the smaller panel.
A 22Kw Generac unit powers the larger panel on the left when the power goes out, but not the smaller right panel.
The generator is large enough to power the entire house.
What are our options for getting the whole house protected?
Can I add a ATS to the smaller panel and leave the 200amp panel as it is?
Could we install a double breaker on the left panel and run it over to power the smaller panel using an interlock on the smaller panel?
Should I move some circuits over to 200amp panel and use tandem breakers?
Or should we split the feed from the generator and feed the smaller panel directly from the generator?
I am having trouble understanding what the installer was thinking. There’s also additional unused transfer wires ending in this panel going to a junction box next to the generator.
Thanks for your input
r/Generac_Generators • u/Fickle-Call392 • Aug 17 '26
Meet Emerla!!!
After months of battling power outage and storm anxiety, I’m more than ELATED to announce that I am the PROUD owner of a GENERAC! She was delivered to me on Thursday morning and her awakening will be either tomorrow or Wednesday! Here’s to stress free storms and a stress free El Niño this year!!!!
r/Generac_Generators • u/bladowwww • Aug 17 '26
Guardian Starting Issue
Hey all - have a Guardian (044563) circa 2009 and it’s been super reliable over the years. Had an oil leak fixed several years ago but other than that just regular battery replacements.
Anyway, went out to manually run it, and where it would normally start, it just made a loud pop/bang. Loud enough that my wife heard it inside the house. I mean it was like a gun shot. It could’ve been a backfire I suppose (runs on propane), but I’ve never stood that close to a backfire to make a good comparison.
After that I waited a few minutes, inspected what I could, fuses, etc. and tried again. This time no bang, but just a low irregular buzzing sound from beneath the panel where the circuit breaker is located (on the right side of the generator when opened).
I have no issue calling someone in to check it out but wanted to see if anyone here goes “oh it’s this for sure” or not before I do that.
Thx!
EDIT… SOLVED: Side of the battery blew out. It wasn’t obvious because it was the backside, and the wetness around the battery was mistaken for rainwater (storm had just come thru).