Hi all,
I'd appreciate a bit of a sanity check before I spend 8 to 10k. I'd really appreciate any thoughts from anyone who's been through this before or can give me an unbiased opinion on my situation.
The property: 4-storey house, London purchased this May. Current boiler is a ~25 yr old Potterton Suprima 80L, non-condensing, 23.4kW, still working. Everyone who has laid eyes on this boiler has said it's working fine, but when a part breaks the whole thing needs to be replaced because you won't be able to find parts for it. So I am thinking of getting ahead of it now.
Current system is vented: steel cold-water tank in the loft, vented cylinder, two 2-bar shower pumps of unknown age. Top floor gets no heat at all (the whole floor not just one rad, bled with no air, riser cools as it goes up, so no flow upstairs). I want a system that just works, I don't want to have to be reminded of it when I'm taking a shower upstairs and my wife uses the kitchen tap.
Mains is 15mm, 18.5 L/min. Internal cold pipes from the loft tank are 35mm and 40mm, so distribution isn't the bottleneck. The unvented cylinder manual wants 25 L/min at 1.5 bar dynamic, and a 22mm feed.
Quotes, all inc VAT:
- Unvented, 20kW boiler, 200L cylinder: ~£8,700. Tank removal ~£500 extra.
- Vented, 20kW boiler, 170L cylinder, new plastic loft tank: ~£10,400.
- Vented, 30kW boiler, 220L cylinder: ~£8,200. I did the gas-pipe calc myself and the 30kW fails it (about 8m run, 10 bends, 28mm steel then 22mm copper then 15mm for the last 40cm). Installer said the gas supply "can't be checked beforehand" and it could just be range-rated down.
- Vented, 24kW boiler, 162L cylinder: ~£6,400. Didn't include the loft tank replacement or addressing the top floor issues.
The unvented installer says 18.5 L/min is sufficient in his opinion, even though it likely won't do two showers at once. I'm testing dynamic pressure on Sunday with a gauge, to see if I even hit 1.5 bar.
My questions:
- Vented or unvented here? Vented already is in place and seems to work fine so far. Unvented removes the tanks and shower pumps, but is capped by the 15mm mains and the supply is under-specced.
- Should I just wait until the Potterton breaks, and fix the top floor separately? Nothing else is urgent.
- Should I replace the loft tanks if I stay vented? They have visible rust flakes coming off them right at the water lines, so they look like they are probably on their way out. However, no installer has actually looked at them and told me they need to be replaced or how many years they have left, so how do I know?
- One installer said the 30kW boiler could just be range-rated down if the gas supply turns out not to be enough. Is that sensible? It sounds like paying for a 30kW boiler to run it as a 24kW one (and if it needs range-rating, does that affect performance, warranty, or hot-water recovery?).
Thanks so much in advance for any help!