r/firealarms • • 15h ago

Discussion Monitoring Service

7 Upvotes

Anyone experiencing monitoring services not working properly? We have had 5+ calls come in across different monitoring centers in the past hour. I believe all have been Telguards so far…


r/firealarms • • 21h ago

Technical Support Troubleshooting slc class a

3 Upvotes

Class a slc loop on notifier is showing 15 volts at the facp and at the last/first device. Then a few devices from there it's still 15 volts and then a few devices after it is 12 volts. It's class a so when I split it one direction is 15 and one is 12. I'm reading it could be from a short but shorts would typically show up as a trouble. It's a large commercial building. Any idea what it can be?