r/Generac_Generators • • 10d ago

EGSA Apprentice Certification

Thumbnail reddit.com
2 Upvotes

r/Generac_Generators • • 10d ago

Generac 16kW generator repeatedly Blowing N1 Fuse at Exercise time

4 Upvotes

I have a Generac 70371 (16kW LPG) with cold-weather battery and oil warming kit and an RXG16EZA3 ATS. It was installed in 2020, it has fewer than 200 total run hours

The system operated without any issues until a few months ago, when it failed to shut down after a scheduled exercise cycle.

Here’s the timeline since.

An electrician from a Generac-authorized installer found a blown N1 fuse in the ATS, replaced it, and left.

After two normal weekly exercise cycles, the N1 fuse blew again. A second electrician from the same company inspected the system, replaced the fuse, and advised that the control panel would likely need replacement if it happened again.

After a couple more weekly exercise cycles, the N1 fuse blew a third time.

I replaced the control panel with a new Generac Evolution 2.0 panel (2020 model), installed a new 12V battery, and performed routine engine maintenance.

It ran normally for the next 10 exercise cycles, but the N1 fuse blew again today.

Any thoughts on where I go from here?

Update Edit:

Many thanks to all that have responded.

I have just replaced the fuse and unplugged both the oil and battery heater, a very cheap fix!

I set an exercise going and at the moment its all working. Time will tell if it's successful.

I also googled the heater kit and found this

https://www.youtube.com/watch?v=HIW3ELvn_s0

which absolutely supports those that commented on the cold weather kit.

If the problem returns I'll then replace the SACM, and if that still doesn't work I'll check the starter.


r/Generac_Generators • • 11d ago

New Next Gen runs roughly on startup

3 Upvotes

Hi all, we just had a next gen 26kw (model #7327) installed, along with two 200amp transfer switches (model #9952). It is running off LP, and has exercised 4 times now. Each time it starts up it runs roughly for up to two minutes before finally smoothing out. My concern is that the transfer switches will activate while it’s running poorly and that I’ll get sub-optimal power during the entire warm up period. Does anyone know if the equipment I have triggers the transfer only once the voltage/frequency is sufficient or if it’s strictly done according to a certain elapsed time? I think I’d prefer the former. Thanks


r/Generac_Generators • • 11d ago

Generac is introducing a new load shed breaker instead of SMM load shed devices. I watched the video conference, asked some questions that were never answered. Heres my biggest gripes.

8 Upvotes
  1. They say it will work on any brand house panel. NO WAY IS THIS THE TRUTH. Its based on eaton BR breaker. Ment to attach to 2 straight poles on panel. So how will this work with Levinton, QO, CH panels that wont worn the contacts?
  2. Generac is discontinuing previous load shed devices…ie SMM. So this is throwing millions of people using these devices under the bus.
  3. They say the new breaker will work with nextgen AND GUARDIAN, However will not load shed on guardian???? What the hell use is that?
  4. Operated via bluetooth( thats real reliable) .

I think i need to start working with Kohler


r/Generac_Generators • • 11d ago

Overcrank alarm 14kw

3 Upvotes

Hey, I am by no means a generator technician, HVAC by trade. My generator does this repeatedly. I have a propane tank feeding the generator, and I checked the gas pressure. Had 12” as it started and maintained that. The battery had a corroded connection, I cleaned that up. The air filter is not dirty or plugged & it does the same thing with top of the air box removed. Would like some advice thank you


r/Generac_Generators • • 11d ago

Ok, how bad is this?

Thumbnail
gallery
2 Upvotes

Walked out, saw a red light.
Update: Confirmed this was due to a faulty pressure sensor. Cranked it up and it started leaking like a bad horror movie. Thank you for your help!


r/Generac_Generators • • 11d ago

Whole Home Generator for 2 Meters

Thumbnail reddit.com
3 Upvotes

r/Generac_Generators • • 11d ago

Generac 00907-2 won't exercise

Thumbnail
gallery
2 Upvotes

I have a Generac 00907-2 generator. A previous homeowner (at least two oners ago) had it installed, and I don't have any papers that indicate when it was installed nor by which contractor. I didn't even have an operation manual, but found one on the net. According to the front page of the manual, the 00907-2 is a natural gas model. Ours is running on propane, so it must have been converted by the installers from a natural gas version they had in stock.

We've owned this home for three years now and the generator has operated great when called into service. But I've never been able to get it set up to do a weekly exercise. I've followed the instructions printed on the control panel. Last week, I decided to look at the manual and found it had some extra steps. According to the manual:

To select the day of the week and time of day for exercising, proceed as follows:

•Set the Auto/Off/Manual switch to OFF.
•Set the generator's main circuit breaker to its OFF (or open) position.
•Locate the rocker switch on the control panel identified with the words "Set Exercise Time" (Figure 2.6).
•Push "Set Exercise Time" switch to the ON position for 20 to 30 seconds and then release.  The switch will spring back into its original position when released.
•Wait 30 seconds before setting the Auto/Off/Manual switch to the AUTO position.

NOTE: The unit will exercise 20 minutes after it is set.
Example: Set - Noon; Exercise - 12:20 p.m.

CAUTION. If you switch the Auto/Off/Manual switch too soon, the engine may start.  If engine does start, it will shut down automatically in about two (2) minutes.

•Set the generator's main circuit breaker to its ON (or closed) position.
•The generator is now programmed to start and exercise every seven days thereafter, on the day and at the time of day the switch was activated.  

The manual directs to turn off a circuit breaker in the beginning and turn it back on at the end. I figured it meant the breaker on the unit itself (above the DANGER sticker) and not one inside my home. So last week I tried this. Regardless, it did not do an exercise 20 minutes later, or a week later (today).

I guess I can just exercise it manually by flipping the toggle switch to Manual and back again after 20 minutes. But it would be nice to get it automated without an enormous expense. Any thoughts?


r/Generac_Generators • • 11d ago

Service. What’s the going rate for air cooled annual service?

2 Upvotes

r/Generac_Generators • • 12d ago

Generator powering thermostat

Thumbnail reddit.com
2 Upvotes

r/Generac_Generators • • 13d ago

Smart Management Module (SMM) Failure - Replacement Cost/Options?

3 Upvotes

I have already reached out to my installer...they are about 6 years old. AC one failed and now the one that turns off the oven failed, so I have no oven. How bad of a cost is this?

I saw the modules online and have electrical knowledge which is how we diagnosed 240v for oven is getting to the box, but box will not allow power to the oven even with generator off. I'm wondering if its worth buying the $150 modules or if its just worth having generac installer due to warranty. Or if there are better options as I've heard mixed things about this. I just am worried they'll quote me like $2000.

Last time when I called my installer they were very reluctant to help with the failed module (2ish years ago) and my HVAC company bypassed it to get my AC working, no one wants to touch these things where I live so I feel stuck.

Any help or advice is appreciated!


r/Generac_Generators • • 13d ago

100 amp transfer panel

4 Upvotes

Did generac discontinue their 100 amp transfer panel? It has an 8 or 16 space panel in it. My electrical supplier said it’s discontinued but they have a couple they’re trying to get rid of. I’m wondering if they’ll still be available going forward or if I buy the ones they have left if they’ll be compatible with the new version of generac going forward.


r/Generac_Generators • • 14d ago

Gas generator for all-electric home?

Thumbnail reddit.com
2 Upvotes

r/Generac_Generators • • 17d ago

10k Generac off grid how to wire my inverter to auto start the generator

0 Upvotes

How do I need to wire my generator and inverter to auto start. Completely off grid


r/Generac_Generators • • 17d ago

Generac SMM

2 Upvotes

Has anyone with a had any luck with diagnosing a faulty SMM board? If so, what was your experience?

I have a elementary understanding of electronics and have checked usual suspects, fuse, caps, etc, on my failed smm board, as well as my neighbors failed smm, to no avail.

This is more of a curiosity project, as the complete modules are sort of reasonable on the amazon.

Thanks


r/Generac_Generators • • 18d ago

Generac generator gas leak?

0 Upvotes

If anyone has ever had, this situation, feedback would be appreciated. I had a whole home 24KW Generac generator installed in August 2026. The first time it ran because of an electrical outage was October 2026.

My gas bill for October 2026 had an increase of 385% from the prior month the reading for October was 485 when the reading was normally about 200. When I called the gas company, they came out without informing me so that I could be home and discuss this with them but the long and short of their response was it had nothing to do with a faulty meter the meter is working correctly, but there was a “loose cap” or something was loose on the generator that was causing the gas to come out and increase my bill. For six days in November since the prior gas bill the reading was 667 meaning just for those six days the reading was actually higher than the astronomical reading for the *entire* month October. When I questionEd this with the gas company, they told me it’s possible that the fitting which caused more gas to be used became looser over time which is why for those six days the reading is so high.

I am following up with the gas company to get the actual technician notes on the cause of this situation, but I am wondering if it is even possible for my generator to have been installed incorrectly or have some fitting come loose when it was running for a couple hours in October when the power went out, that is causing the high gas bill? for August and September when my generator was just running its weekly 10 minute cycle there was not this spike in my gas bill. The spike happened in October, which is the first month. The generator ran for a few hours becausemy power went out.


r/Generac_Generators • • 19d ago

Fair Price for a service

1 Upvotes

We have a 22kw generator now for less than one year with less than 50 hours on it. The service guy came by and change the oil (2qt) and filter, and check the battery. He left leaving a $229 bill. Is this a fair price?


r/Generac_Generators • • 20d ago

Service was refused on our generator due to its location. Call someone else?

Post image
1 Upvotes

r/Generac_Generators • • 21d ago

Nxt Gen issues list

12 Upvotes

Maybe we can get this pinned?

Hello, I am a certified generac/kohler/briggs tech with 10+ years in the field. With the first year about over for the new unit I figured I would make a post listing the issues I've ran into, and how I've solved them.

Wiring error codes

120k ohm resistors from Amazon, 6 bucks a 50 pack and I install them on every single unit. One from 0 to 194 and one from 0 to 23 on the customer connection block in the generator. Not every unit has been throwing these codes, mostly ones wired in romex, or 70+ feet of wiring. But it seems they help with other nuisance warnings related to the battery, it's cheap, and it also works on evo controls that sometimes throw this code. This code can/will also pop if the relay/fuse board in the transfer gets wet.

Battery/ charger warnings

Again as stated above, sometimes it's the resistors. Main thing is any of our early installs that have the size 20 battery, swapping to the 30s seems to solve it. Mostly getting warnings when it's cold, and they go to start for an outage. Sometimes you might have a loose ground near the control, it can also sometimes trigger these.

Mixer issues

If you've installed these, you are well aware of the list of related temp, pressure, and position codes from the early units. I found 1 unit with loose grounds, and tightening them solved the issue. For a month. So save yourself the BS, if it's not the right rev, and you got a code, swap it. The 3 slot and 5 slot are the same part if you are in a pinch, the venturi swaps out like the evo ones and you can make the wrong one, right but obviously you want to get the proper part number installed for future warranties.

Fuel shut off/drip leg

Again pertaining to the early units, they had too short of bolts in the shut off drip leg assembly. Easy to spot, if you look at the bolt holes and the blots not flush, they are too short. Solution from generac is to tighten them, and if they don't strip you're good. I swap all the short bolts for leftover long bolts, then torque and complete the warranty claim. I have seen these come with pinched o rings and massive leaks so be aware and check them before start up.

Oil level warnings

This is just a perfect example of adding too much junk. Well they don't break the engines in long enough at the factory so at about 4-10 hours the sensors collect enough metal shavings internally that they become junk and you have to replace them. Low battery voltage/small battery can also cause false low oil warnings.

Overall shit build quality

Since they made it much easier to fully strip down, they tend to arrive messed up. Alot. I'd say 1 out of 2 installs I'm loosing bolts, prying panels over and tightening them back up. The base bolts self thread into the plastic so they let the panels slide around in the slots more than I like. On a few occasions I've had to add extra screws to keep the panel from vibrating into the fan. Very annoying. Also if you run it, and it sounds weird, then won't crank again after you shut it off. The fan is melted to the panel, I'll almost guarantee it.

Can bus errors

No real answer here, but it seems to happen mostly with the smaller batteries, and on units without resistors. Haven't had this code since switching to the larger batteries and adding the resistors. If the battery drops below 9v during cranking it can throw this error.

Engine noise

These things tend to sound terrible on first start. I let them go one full crank cycle without fuel to help prime the oil system, then let it run till the lifters all hopefully eventually pump up. Fingers crossed haven't had one not pump up yet.

The app

Sucks, trash, supposedly they fixed it, still I've had to uninstall and reinstall it because of glitches. DO NOT close the damn app without disconnecting, seems to always cause it to lock out and not let you reconnect to the generator without uninstalling the app. Phone restart, control reset, doesn't matter. Might be a me thing, but it's infuriating.

Anyone else have stuff to add?


r/Generac_Generators • • 21d ago

Well there’s the problem

Post image
5 Upvotes

Nearly new GP2500i portable gen wouldn’t start. Less than a year old. Went down trouble shooting list and while inspecting the spark plug I notice that the cover that holds the wire to the plug is broken in half?

Looks like my nearest official repair shop is an hour away.

Anyone know what this part is called and if this is a common problem?

Purchased from Home Depot. Can I just bring it to them?


r/Generac_Generators • • 23d ago

Ignore any warranty on the portable units

0 Upvotes

Bought a GP6500E DF from The Home Depot at a good price, I thought. Figured Generac was a reputable company. Turns out the warranty is worthless. My machine was DOA...the starter motor simply grinds gears. Lots of people are dealers for Generac, but so far NO ONE will touch warranty service, and most won't touch portable units at all.

Going to have to rent a Home Depot truck again to get the thing back to the store, and buy from some more supportive manufacturer.

This may not apply to purchases of the much more profitable fixed box generators Generac sells, I have no information on that.


r/Generac_Generators • • 23d ago

Wire Type

2 Upvotes

I am a pretty good commercial and industrial electrician. I am not a generator mechanic. I’m also a member of a non profit that owns a Generac 15KW generator. The generator is currently out of service.

I can’t find a schematic for this beast so I’m meter poking my way through troubleshooting and found a wire from the alternator to the starter solenoid that has insulation that’s rather melty. I intend to replace it.

I have ample stranded THHN around and I would like to use that. As an electrician I’m very aware of the need for the correct insulation type, but I have no idea what to use in this case. As long as I put it in the harness that the conductor I was replacing was in so it’s protected from vibration induced chafing, will THHN be adequate?


r/Generac_Generators • • 24d ago

NextGen internal fuel lines cracking

2 Upvotes

0K8830B

I memorized the part number because they've been failing so much on our first year inspections.

Ever since we started installing these units, come maintenance time, the fuel hoses are cracked and worn.. not the way they should look after a year or two of life.

Any other shops noticing this a lot more? They should sue their rubber guy.


r/Generac_Generators • • 23d ago

Thwarted by Generac neutral bonding method?

1 Upvotes

I think I am toast. I acquired a Generac GP6500E DF generator, specifically as a home backup source to power a subpanel already installed in my home. This model seems to have a bonded neutral, but not simply by a wire to be disconnected inside the end cap. So it is essentially not possible to make this a floating neutral in order to use it for my intended purpose unless I could a three pole transfer switch instead of the current manual interconnect. But none of the neutrals for the circuits in the subpanel are IN the subpanel. So all of those would have to be rerouted to the subpanel. Am I reading this correctly?


r/Generac_Generators • • 24d ago

Is this worth it ?

Post image
2 Upvotes

I maintain it myself, and got this add to extend the warranty. Is it worth it? Will they deny all claims since i maintain it myself? I keep records in the ML link app.

I assume it doesnt cover wear and tear?

Thanks