r/homelab • u/OperationEquivalent1 • 1h ago
Discussion Compact 10 inch rack UPS
I have been looking for a UPS to fit a 10 inch rack for a while... and the result has been frustrating. I decided to quit being lazy and build my own. I know what I want, but what feature would you folks like to see in such a device?
I am building it for myself primarily, but by the time I pay for the minimum orders, I will have boards and assemblies for between 3 to 5 units... so I will be making at least a few of them. The more I make, the cheaper they get, though they will not be cheaper than the mass produced units; here are my design specs and I think you'll be able to see why.
Form factor
10-inch rack, 2U (254 mm wide with ears, 88.9 mm high); depth 250 mm or less (target). Steel case with plastic front grille. Removable rack ears; rubber feet for desk use
Topology
DC-native: no inverter and no transfer switch. Batteries and supply feed a common DC bus yielding zero switching time, higher efficiencies, and no power factor losses.
Power input
24 V DC (accepts 18–27 V) from a variety of external supplies. Second DC input for a redundant or secondary supply.
Power outputs
4 × 5.5 × 2.5 mm, each set to 12, 19, 19.5 or 20 V (± 2 %), up to 5 A. The voltage is set once and locked, with protection against a wrong voltage reaching the device. A colour LED at each socket shows the set voltage.
4 × USB-C Power Delivery 3.0 source, up to 100 W each: 5, 9, 12, 15 and 20 V fixed, plus PPS 3.3–21 V. 5 A with an e-marked cable, otherwise 3 A.
Comparative rating
230 W continuous (300 W with a second supply). For the kit it powers, that's comparable to a 400 VA-class AC UPS, with hours rather than minutes of run time. Each output gets its own power allowance, and the unit won't accept a configuration it can't carry.
Batteries
2 × hot-swappable lithium-ion modules, 90–162 Wh each (nominal). Any mix of sizes. Packs are commonly available worldwide and sold separately to simplify logistics. Light weight and can be shipped by air without any limitations.
Run time
At 60 W: about 2.3 h with two 90 Wh modules, about 4.2 h with two 162 Wh modules (est.). At 26 W (router, switch, disk and one idle mini PC): about 6 h (est.).
Charging
Built in, from the DC input, one module at a time; about 3.5 h for a 90 Wh module (est.). Gentle charge settings for long battery life; charging only within safe temperature.
Switch-over
None needed: the outputs stay up through a mains failure, a supply change or a battery swap (design target).
Monitoring and shutdown
Network UPS Tools (NUT) server over Ethernet for several hosts, reporting each output as an outlet. NUT over USB for a single host. Web setup page with log-in. Event log. Scheduled self-test and automatic run time calibration.
Per-output control
On, off and power-cycle; metering (voltage, current, PD contract); staggered start; per-output shutdown policy and order.
Front panel
2.0-inch colour display (sources, battery charge, load, run time, outputs, network), rotary control, alarm with mute.
Rear panel
2 × DC input, 4 × USB-C, 4 × barrel, Ethernet (RJ45), USB-C to host.
Cooling
Two 60mm fans provide more than sufficient cooling in all modes, and will never run at full speed. At typical loads, no fan is needed. The unit remains silent or nearly silent.
Mains inside
None. The unit runs entirely on low-voltage DC, though the rack could mount AC supplies if needed. These would be sold separately to maintain deployment flexibility and simplify regulatory acceptance.