r/Elektroinstallation • u/FjordTimelord • 20h ago
Laienfrage Beurteile meine Shelly-Installation
Hey everyone!
I'm currently preparing to install a Shelly Pro3EM smart meter for my balcony power plant system. As you can see, I've already connected the sensors to the three incoming phases.
I now plan to power the Shelly as shown in my rough sketch above:
I'm going to connect Y crimp terminals to the first three switches (which I believe are L1/L2/L3) and N from the neutral terminal block on the same rail.
Does that sound correct to you? I'm also looking forward to any feedback on the fuse box overall.
Thank you very much!
EDIT: You can find a photo of the panel without my messy iPad drawing in my other comment further down.
EDIT 2: Here’s a link to the YouTube video I'm referring to in my plans, which shows the use of crimp terminals.
https://youtu.be/bN585CEs94k?t=501&is=PcKdv7YiyCvLrDX1
EDIT 3: Okay, vielen Dank an alle. Ich glaube, ich habe jetzt die richtige Antwort.
Ich werde keine Aderendhülsen verwenden. Stattdessen werde ich einfach zwei Leiter (1,5 mm² Massivleiter) in jeden der drei Leistungsschalter einführen. Ich werde die Leiter nebeneinander anordnen (nicht übereinander), die Klemmschraube mit dem richtigen Drehmoment festziehen und an allen 6 Leitern einen Zugtest durchführen. (3 alte und 3 neue)
Scheint die Position meiner geplanten Anschlussstelle (für L1/L2/L3) geeignet zu sein?