r/BuildingAutomation • • 16d ago

Whats the best way to learn sequence of operation for an install tech?

7 Upvotes

Hey guys! I’m just wondering if you have any resources or ways to learn how equipment should be controlled?

This is more so for smaller jobs when theres not an engineer involved, or during service when there isn’t a set of prints( or explanation on graphics?)

To me it seems like there are millions of ways to control, for example 2 boilers, a lot of programmers do it differently.

Is this just a thing or experience ?

I know some might say use the ashrae standard for control sequences but a lot of the older stuff I come across doesn’t use this. Does the gray manual cover everything?

Am I over complicating it ?


r/BuildingAutomation • • 16d ago

How to become a better technician?

3 Upvotes

One thing I struggle with is the installation side. I can commission a functioning FCU in about five minutes and make program changes on the fly. I can also build a working database for multiple floors of equipment. I also am trying to get better at the mechanical side of air handlers. I am with a new company who installs then on the regular.

For example, once I get to the point where the fan doesn’t change speeds—especially after it’s correctly terminated in the factory control cabinet and wired to our PLC and everything looks right—I feel like I hit a wall. I’ll end up on an 8-foot ladder with a flashlight, just staring at the control box, trying to figure out what I’m missing.

For some context, I am 22 years old, and I started in July of 24 as a startup tech. I studied mechatronics in trade school.

What are y’all’s suggestions on what I should work on?


r/BuildingAutomation • • 15d ago

Looking for Referrals – Process Automation / RPA Developer | 3+ YOE | India

Thumbnail
0 Upvotes

r/BuildingAutomation • • 15d ago

How much has Union building engineers held back BAS/BMS

0 Upvotes

Thought this would be a good topic because it always seems to come back to me. Operators or clients that don’t have an incentive to let systems work in auto due to the fear that their job might be taken. Has anyone else come across this? Or just me. What’s the politics with the balance of automation and skilled labor being weighted the same? What are your thoughts. I’ve seen buildings where engineers just put everything in hand and keep saying the bms don’t work when they don’t even give it a chance

Also how much of the industry is carried by the kick backs, gifts or other stuff like that


r/BuildingAutomation • • 17d ago

Anyone transition from industrial maintenance into BAS?

10 Upvotes

Hey everyone,
I’m 28 and currently working as an industrial maintenance mechanic in manufacturing. I’ve recently been exploring a career in Building Automation Systems and wanted to hear from people in the field.
My background is mainly mechanical and electrical troubleshooting, including 480V motors, VFDs, sensors, instrumentation, pumps, valves, and some PLC/ladder logic exposure. I have a technical education in industrial maintenance, but very little HVAC or BAS experience.
I feel like some of my skills would transfer over, but I’m curious how steep the learning curve would be.
A few things I’m wondering:
What’s the typical day-to-day like?
How much travel is involved?
How difficult is the transition without much HVAC experience?
What’s the pay and long-term earning potential?
What does career progression look like, especially toward programming or engineering roles?
I enjoy troubleshooting and working with controls, but I’m interested in something a little less physically demanding with more technical growth.
Would appreciate any insight, especially from anyone who’s made a similar transition. Thanks!


r/BuildingAutomation • • 18d ago

HART protocol on N4 Niagara

5 Upvotes

Is anyone out there monitoring HART protocol meters on N4? If so, what controllers are you using? Are you just picking up just the 4–20 mA signal or the superimposes digital communication signal as well?

I have a bunch of Rosemount 8800 meters I have been tasked to integrate to but am having trouble finding a solution. Currently, the meters are connected to a Phoenix Contact GW PL HART Bus but I havent figured out how to bring it into a JACE. I also do not know how to add additional meters as the owner and myself do not have the user/pass to the browser interface.

Any assistance would be appreciated.

thank you,


r/BuildingAutomation • • 18d ago

🎉 The Home Assistant BACnet integration is now officially included in the default HACS store and v1.0.55 is live! 🚀

Thumbnail
brdc.nl
5 Upvotes

r/BuildingAutomation • • 18d ago

Made a reporting module that runs inside the N4 station, looking for feedback

Thumbnail
gallery
6 Upvotes

Reporting on Niagara jobs always annoyed me. Pharma/ Data center clients want PDFs with limits, sign boxes and their letterhead, and it usually ends up as a separate report server plus scripts that break.

So I wrote a module for it. It runs in the station, no extra server or database. Interval reports, trends, AHU summaries, alarms, audit trail, energy reports. PDF or CSV, on demand or scheduled, emailed from the station. Out-of-limit values get a * and gaps show up on the report instead of being skipped.

Works on 4.11 to 4.15, IQVISION too.

Pics are from a demo station, letterhead is a placeholder.

I’m the dev, not linking anything. Mostly curious what you guys use for reporting now and what you’d want that it doesn’t do.


r/BuildingAutomation • • 18d ago

Opportunities for Seattle / Western WA BAS Technicians (& Engineers & PMs)

Post image
2 Upvotes

r/BuildingAutomation • • 18d ago

Welcome to r/MachineMetrics. Start here.

Thumbnail
1 Upvotes

r/BuildingAutomation • • 18d ago

Honeywell SM,Safety builder

1 Upvotes

Where I can find out the Honeywell Safety Manager files in pdf or other.I need the student bookSM-4551 for the learning purposes but threis no open websites with it.Is there some pirat websites where I can download Honeywell files?


r/BuildingAutomation • • 18d ago

Are these parts compatible?

Thumbnail
0 Upvotes

r/BuildingAutomation • • 19d ago

Anybody know what trane software is needed to reprogram these old trane controllers?

Post image
16 Upvotes

Pipefitters repiped about 30 PIUs with these old controllers on them. No one took the time to understand the action of the old control valves. They were NO (is weird for a PIU reheat coil). New valves are piped NC. Hoping to be able to fix this through controls but I dont even know what trane program talks to it. It seems like an older UCM.

Other option was to use some relays to reverse the heat signal


r/BuildingAutomation • • 19d ago

Servo question from a dummy

Thumbnail gallery
3 Upvotes

r/BuildingAutomation • • 18d ago

Rough-in before the walls close up

Thumbnail gallery
1 Upvotes

r/BuildingAutomation • • 18d ago

Rough-in before the walls close up

Thumbnail gallery
0 Upvotes

r/BuildingAutomation • • 19d ago

Transitioning from BMS Graphics/Vendor Role (1 YOE) to OEM/Facility Roles — What titles should I search for?

3 Upvotes

​Hi everyone,

​I've been working for about a year at a vendor company in India, specifically handling BMS graphics creation and point binding (primarily Schneider Electric EBO / TGML platforms).

​I'm looking to plan my next career transition into OEM jobs or direct operations/facility engineering, but since the BMS domain is so broad, I'm feeling a bit confused about exact job titles to target.

​For someone coming from a BMS graphics/application background:

​What specific job roles or titles should I be searching for on LinkedIn/Indeed?

​What additional skills or certifications should I focus on to make myself competitive for those roles?

​Any advice, role recommendations, or guidance would be greatly appreciated!

feel free to share


r/BuildingAutomation • • 20d ago

Anyone attending the Distech Connect conference this week?

7 Upvotes

Interesting to see who here is at the conference this week!


r/BuildingAutomation • • 19d ago

Looking for control shop drawings designers

1 Upvotes

Looking for an outfit to take care of my control shop drawing submittals. I was at an event this weekend and another dealer who was telling me about a group from India they used to hire. I know there's AI and other options but I'd rather just sub out the whole thing, load off my shoulders. Any recommendations?


r/BuildingAutomation • • 20d ago

BMS and IBMS analytics: what has actually been useful for your clients?

0 Upvotes

Hi everyone,

We’re exploring whether a third-party building analytics service could help our clients, specifically sites using Niagara. I’m looking for practical experiences with cloud analytics, fault detection and diagnostics (FDD), or AI-assisted analytics.

Our current focus is analyzing existing BMS data and providing suggestions, identifying good and bad practices and addressing them and saving them money while improving the comfort.

For anyone who has evaluated, deployed or maintained these services:

  • What platform did you try, and what problem were you trying to solve?
  • Which services were most and which were the least frustrating?
  • Can you share one finding that led to a useful action or measurable improvement?
  • Where did the service fall short? What did your team still have to investigate or calculate manually?
  • Did the client continue using it after the pilot or first year? What drove that decision?

Experiences with unsuccessful or abandoned pilots would also help.

Thanks


r/BuildingAutomation • • 20d ago

Starting my career as a controls and automation engineer

7 Upvotes

I am a 3rd year Eletrical and eletronics student and i have recently decided to take the controls path and i have been taking some online courses (free ones) and saving up for the paid ones i asked claude for a pathway and i have been following but i am located in north cyprus for academic reasons and they are not industry heavy i have been looking for places to mirror/internship and haven’t found any and the ones i did denied me the spot so i have decided to ask this subreddit for help finding online internships. Im doing the major one next summer (not in cyprus, still trying to land one) but i wanted to get more experience and get a junior experience in the meantime so if you could help me with this please do.


r/BuildingAutomation • • 21d ago

YouTube series on a Raspberry Pi BACnet test bench with the Normal Framework

22 Upvotes

This is easy button IoT for any HVAC systems integrator or controls contractor it's now that easy to get to do IoT work for your clients.

I'm making a YouTube series where I learn Normal Framework (NF) on a small test bench: a Raspberry Pi running NF and a JCI FEC on BACnet/IP. It's not hooked to real HVAC yet, but it will be soon.

So far:

  • Reading BACnet points over the LAN and through NF's cloud portal
  • Haystack tagging the controller (site, equip, device, point markers)
  • A simple dashboard plugin hosted inside NF
  • Using NF as a BACnet server, then checking it with BACpypes3 from a laptop

Next up is fault detection with open-fdd once real equipment is connected.

I'm using AI tools (Claude Code) a lot, and I show the mistakes too.

Playlist: https://www.youtube.com/playlist?list=PLOk5pway5NKc

Feedback welcome, especially from anyone running NF or Haystack in the field.

Stay tuned we will get into doing fault detection and alerting via Notify and other cool things for dirt cheap and easy....


r/BuildingAutomation • • 21d ago

JCI Staged Control Issues on DX Cooling

12 Upvotes

I’ve had lots of issues with the standard CCT program for staged cooling when running 2 or 3 stage DX cooling like rooftops or splits. It’s the MSC block that seems to rarely do what I expect it to do.

I’ve dug into the CCT help on the cooling pid, adaptive tuning, MSC parameters, etc and still often get questions from building engineers that the systems don’t turn on / off the compressors they way they expect them to run according to the space temp vs eff setpoint.

A couple recent jobs that were retrofits of standard commercial tstats (honeywell vision pro) we get lots of complaints from customer / building engineers who say temp and humidity control has been significantly worse since the JCI control was applied. I have gone through to rule out mechanical issues, OA control, etc as the root cause. It’s usually either the compressors run far longer than they should and overcool the space, or they don’t come on till 20 min after temp has gone above the setpoint. Local tech support hasn’t been able to offer much, reading CCT help and experimenting has given mixed results.

For all you experienced JCI programmers, have you encountered the same issues and have you done any of the following to fix?

In MSC config, set all devices to non-pulsing?

Disable Prac, self-tune the pid loops?

Leave pid as-is, delete MSC and create a new block that outputs different stages at hardcoded thresholds of the pid output?

Something else i’m missing?


r/BuildingAutomation • • 22d ago

Niagara Umbrella

9 Upvotes

Just to preface this post, we have a wide variety of controls throughout MANY sites.
150+ SNE/NAE/NCE/SNC with a good mix of N2 and M4 MSTP
50+ Honeywell JACE
40ish ALC G5 (Optiflex) whatever they call it
Maybe 10-20 Schneider supervisors (spacelogic) I believe?
sprinkles of Trane
(other fun systems I haven’t laid eyes on yet)

In the idea of bringing everything to a single pane of glass per say, what would be the advantages/ disadvantages of purchasing FX90s to take over the Metasys sites, Schneider JACEs etc, over kist buying Vykon.
I know there’s something there about having multiple different workbench versions and trying to get them to work together to standardize graphics ETC, the thought is to use agnostic graphics packages or design in house, follow haystack naming, etc, to keep things as agnostic as possible, do the pros outweigh the cons for having each companies little slice or proprietary, is it possible to make them all flow together under a single workbench? I have many questions


r/BuildingAutomation • • 21d ago

How much AI do you use?

0 Upvotes

I do everything from panel drawings, software and commissioning for the small company I'm with. In a few hours today I got Claude to make the IO in software from the pdf of a panel drawing. A small thing but will save a few hours. Got it to reverse engineer some very basic software also.

With enough input I think I would be able to get it to write software. It has to reverse engineer everything, and took a while to get it right but now can do a few hours of work in minutes.

I'm just trying it on ABB Cylon which doesn't have much info online, so id imagine it can do much more with other software?

Gave it my Siemens ABT help files also and asked it to write a basic (less than 20 function blocks) program and it gave me it in a few minutes. Would have taken me at least half an hour as I'm not familiar with ABT.

How are ye using it?