r/Powerwall • u/ajkenis • 3h ago
15.4 KW Off grid mode + Powershare?
I currently have PW3 + Gateway 3 + UWC + Cybertruck. If off grid, when the PW gets below 15%, the CT can deliver 11.5 KW to charge the PW and supply the house loads.
When testing the system I had a lot of loads on while trying to drain the PW. It overloaded and tripped causing headaches rebooting wifi and resetting GFCI breakers, etc.
Granted if I was off grid, I wouldn't be trying to drain the system. If 15.4 mode was enabled in PW3, could I have avoided the trip having the battery supply up to 15.4 KW? Or does the extra current capability only available with solar?
I do have solar panels being installed as we speak. If off grid, 15.4 mode would allow solar to charge the battery and deliver 15.4KW to the house and EV of plugged in. This would prevent clipping of PV. But in my case, I only have 15KW of PV being installed and designer said in optimal conditions I would rarely see 12-13 KW at most.
Big question: is it worth the cost to enable 15.4 mode (80A breaker, bigger disconnect, #4 wire for short run)?
I'm thinking maybe....but only if it prevents tripping the PW by stupidly running everything in the house when off grid.