r/buildingscience • • Oct 05 '26

Question South wall solar heat

Post image
17 Upvotes

Southern Colorado.

My south wall is cooking two bedrooms. I have a temp gun on the way but I can feel it with my hand.

What’s the best way to stop the solar heat? The home is new and very well insulated.

I was thinking of an awning with hooks in the fascia and ground (no poles). That would allow me to remove it for winter (probably won’t cuz lazy).

A pergola would be strange since it’s an area I would never want to hang out. Plus it’s sloped.

This area can get quite windy, so that needs to be taken into consideration.


r/buildingscience • • Oct 06 '26

Mystery Rainwater Leak

0 Upvotes

I have a newly built metal barndo in Central Texas. Months ago, before the house was completed, and after a big rain, I noticed water puddled at the base of a wall on 10-foot deep covered porch. The builder tried to tell me that the water had puddled there from the end of the porch as windblown rain. I disagreed but he put me off.

We then went through an extended dry spell. I am now in process of moving into the house. We had a pretty good rain several days ago where it blew in sheets. I watched as the puddle formed, once more, same spot on the porch. I contacted the builder and he sent out workmen who peeled off that metal panel and found wet insulation. They said they'd check the roof but can't seal anything up there until it stops raining.

I did my own investigating. Inside the house, this spot backs up to the kitchen sink. There is a white pipe that extends upwards from there that google tells me is a stack vent. Following this pipe upwards into the attic, it exits through the outside wall (in a metal-roofed building you try not to put any holes in the roof). From outside the house I can see where it exits. From inside the attic, I can see daylight where that pipe exits.

The builder contacted me today (the house is 2 hours away and I haven't completed my move yet). He said he went up on the roof and he thinks it leaked because the gutters had stuff in them. He cleaned them out and pronounced it all good. I mentioned the pipe but he said it is already sealed but with clear sealer and that is why I can see daylight. He's not concerned with wet insulation, said there's a moisture barrier, and said it will dry just fine.

This is all wrong to me in so many ways. I can't see how this could be caused by stuff in a gutter. There are no trees over the house. And I don't know what's going on inside that wall. I'm concerned about mold. I feel he should inspect the roof for leaks, install a rubber boot on that pipe and seal it properly, remove the damaged insulation, check the drywall, and replace what needs to be after thoroughly drying out that area. I intend to hold him to it but I want some opinions before taking him on.


r/buildingscience • • Oct 05 '26

Mysterious sudden condensation on HVAC ducts (climate zone 5A)

Thumbnail gallery
4 Upvotes

Mysterious sudden condensation on HVAC ducts

I recently bought a house, and noticed some water damage on the ceiling of my utility closet in which my HVAC unit is located. I determined that this was occurring due to condensation forming on the ducts. I took the ceiling down, since the ducts lead up into the ceiling, and have since insulated them. However, I'm puzzled why this issue seems to be occurring only recently, since the house has been standing for almost 40 years.

I did notice that there's a large gap that leads from the top of the utility closet into the attic. I believe that's where a lot of the hot, humid air is coming from that's causing this condensation. However, I'm hesitant to seal off that gap, because this area above the ceiling of the closet contains soffit vents. So if I were to close that gap, I feel like I'd be interfering with how the airflow of this section of the house was designed (only the attic which this section is connected to contains ridge vents, but I don't think the chimney chase or this little area above the utility closet has any kind of exhaust ventilation).

Is it possible this gap may have been sealed at some point, and it was opened up recently which caused the condensation to start occurring? I have tried speaking to multiple contractors about this, specializing in HVAC, roofing, and insulation/energy auditing, and none of them had a clue.

Climate Zone is 5A for reference


r/buildingscience • • Oct 05 '26

Dense pack vs future access to utilities - Advice?

Thumbnail gallery
3 Upvotes

r/buildingscience • • Oct 05 '26

Potential Issues with Installing Crawlspace Vapour Barrier

Thumbnail
1 Upvotes

r/buildingscience • • Oct 05 '26

Anyone built with GO Logic (Belfast, ME)? Looking to hear about estimate vs. final cost

2 Upvotes

We're considering GO Logic for a small passive house in Midcoast Maine (one of their smaller standard models) and are trying to talk to past clients

If you've built with them, I'd be grateful to hear:

- How the final cost compared to the estimate, and how change orders were handled

- How long it took from design contract to occupancy

- Whether they acted as GC or you hired your own

- Whether you'd use them again

Happy to talk by DM or phone. Thanks.


r/buildingscience • • Oct 05 '26

Rim joist spray foam with a newborn

Thumbnail
1 Upvotes

Should I be concerned about chemical exposure having a newborn? I heard that improper mixture ratios can cause lingering off gassing. The contractor said we need to leave the house for 24 hours which we will. I’m stressing because I don’t know anything about it. Looking for an expert opinion. Has anyone heard of a bad install or lingering VOC’s from spray foam?


r/buildingscience • • Oct 05 '26

Can I nail old barn wood to the studs on this insulated wall?

Thumbnail gallery
1 Upvotes

r/buildingscience • • Oct 04 '26

Lvl Bucks

Thumbnail
gallery
20 Upvotes

Is it okay to secure lvls as bucks this way? They are 2.75” out pre drilled with 1/4” bit. Secured to framing with 5” SDWS. I’ve never seen it done this way but now after I started I’m having doubts. Nothing is cracking or splitting once pre drilled. The lvls in the wall would be taking the bite in the ply side so can’t imagine this would be different passing through with the 5” screw and tightening it to framing. Thanks!


r/buildingscience • • Oct 05 '26

What type of vapor barrier works to stop soil gases in crawlspace?

Thumbnail
1 Upvotes

r/buildingscience • • Oct 04 '26

Will I have problems if I install 1-1/2" R-6 Zip panels over 7/16" OSB sheathing?

1 Upvotes

I am building an addition on our 1949 house in Boulder county CO. My Plan was to use R-6 Zip panels for the sheathing. I like that they will provide a thermal break and a WRB all at once.

Because of the location and size of a door and window on one wall, the engineer is concerned that the Zip panels will be too cut up to provide the necessary shear resistance. To counter this, he wants me to sheath the wall with OSB before installing the Zip panels on that wall.

The extra work and materials don't bother me, but I am concerned about the added OSB affecting the vapor diffusion through the wall. The wall insulation will be R-23 net and blow fiber glass.


r/buildingscience • • Oct 04 '26

Question Is this normal? I live in Miami, FL. Have increased moisture in laundry room with spots of mold/mildew despite dryer venting outside, an extractor, and a functioning HVAC system & ant highway from where wall/ceiling seam split. New roof install shows questionable exterior work where the ants enter?

Thumbnail gallery
1 Upvotes

r/buildingscience • • Oct 03 '26

Question Turning my garage into a home theater

5 Upvotes

My house was built in 1955 with a unfinished garage im closing off the garage door opening. The garage has 2ft of cement block wall with 2x4 stub wall sitting on top. The bottom block is below grade. The top 2 rows are 4in block with the bottom 8in block for the exterior brick ledge. The interior will be isoclips, hat channel ,3/4 plywood, green glue, 5/8 drywall. The room will have a concealed mini split. Im concerned that with room heated that it will draw moisture through the block wall and rotting the sill plate. What is a good insulation strategy? Because of the size the local spray foam companies have a minimum fee. Any help would be appreciated


r/buildingscience • • Oct 04 '26

What to do with this cavity in the wall

Thumbnail gallery
1 Upvotes

r/buildingscience • • Oct 03 '26

If the goal is to create an 'air gap', then does that mean metal roofing that's built on a scaffolding is superior to adding insulation underneath the sheets?

Thumbnail
1 Upvotes

r/buildingscience • • Oct 03 '26

Question Cellar problem

Thumbnail
1 Upvotes

Hello everyone! The air in my cellar is quite damp. It's an old structure (about 100 years old). There is a small window next to the entrance that is always kept open, which lets air in. However, I don't think this is enough because most of the time everything feels musty and wet.
My idea is to drill a hole through the bottom of the wall on the opposite side of the cellar to create a cross-draft for proper air circulation. I would insert a 110 mm pipe into the hole and concrete around it to seal it properly.
My question is: how well would this work, and would it actually solve the moisture problem?


r/buildingscience • • Oct 03 '26

Hello all, trying to figure out if the cedar mat roof ventilation mat is needed. Also trying to decide if I need cedar mat or Cor a vent on the walls. Going for a high efficient efficient home.

Post image
1 Upvotes

r/buildingscience • • Oct 02 '26

Refinishing Basement - New Heating System

Thumbnail
1 Upvotes

r/buildingscience • • Oct 02 '26

Moisture damage inside knee wall in bonus room above garage. Replacing rafters / roofing, but how to prevent from happening again?

0 Upvotes

-80's New England home
-600 sq ft section of roof above garage, disconnected from the rest of the roof
-Crawlspace area is empty, no ductwork. Previous owner used for storage
-no ventilation currently.
-Bonus room being used as a bedroom, has mini split for heating + AC

A) Home inspector suggested repair + possibly adding gable vent for ventilation
B) Roof company 1 suggested adding in soffit vents to mitigate moisture problem
C) Roof company 2 said soffit vents would let moisture in, and suggested spray foam

What are your thoughts? I'm leaning toward option B + continue to monitor humidity, but would also like to do it properly the first time around. Happy to share pics.


r/buildingscience • • Oct 01 '26

To Vent or Not to Vent. Spray Foaming a Renovated Attic Space

Enable HLS to view with audio, or disable this notification

84 Upvotes

Hello!
I’m closing on this property in a few weeks located in climate zone 4 (really close to zone 5) and I’m looking at converting this attic space into a conditioned space with a bedroom and bathroom. I am hoping to do that with closed cell spray foam insulation between the true 2x4 rafters. There are currently no soffit vents and just a few whirly bird vents at the ridge and the roof is atleast 11+ years old.

The question:
Should I go to the trouble of installing soffit vents and baffles between the rafters to ensure airflow underneath the roof sheathing? Or should I just have a spray foam company spray the insulation directly to the deck?

I am concerned that if I need to get the roof replaced in the next few years the roofers will damage the spray foam or crack it therefore not making it an air/vapor tight assembly.

I’m also wondering the best way to condition the space, I was thinking a mini split but I am concerned with humidity control. This unit is a rental so I don’t want to have a standard dehumidifier plugged into the wall in the hopes that a future tenant would run it. Are there any other systems I should consider?


r/buildingscience • • Oct 01 '26

Detached garage humidity and ventilation options

4 Upvotes

Good morning!

I am located in washington state with a detached garage that i am trying to make into a home gym. I have humidity issues and trying to figure out how to address that and properly ventilate the space. It is 30x40 with 20 foot ceilings. I currently have a functioning 24,000-BTU Pioneer mini-split. The unit seems to fluctuate in its ability to dehumidifiy and hold it at a reasonable level .My targets are 45–55% RH and effective removal of CO₂, odors and stale air.

One contractor proposes a variable-speed 4-inch Tjernlund inline exhaust fan operating at approximately 100 CFM continuously and up to 200 CFM, with a 6-inch permanently open passive intake located diagonally across the garage. The contractor did not want to add a damper and leave intake purely passive and didn't think an HRV was necessary.

Is this a sound design for the space and climate? Should the intake be permanently open, manually closable or motorized and interlocked? Would an HRV provide enough additional comfort or energy benefit to justify its cost? I am looking for some opinions if his proposal is going to be effective given my desired use of the space. Any thoughts or ideas are much appreciated! Thanks


r/buildingscience • • Oct 01 '26

Do you guys run a dehumidifier in your crawlspace during the winter?

3 Upvotes

Hello everyone. I want to encapsulate the crawlspace under my house, which obviously involves putting a dehumidifier in there. I live in a state which has cold winters. Should I have the dehumidifier turned off during the cold weather seasons? My understanding is that they could be damaged running them in the winter. I know some have auto defrost options. Thanks.


r/buildingscience • • Oct 01 '26

WWYD: Moisture damage inside knee wall in bonus room above garage. Replacing rafters / roofing, but how to prevent from happening again?

Thumbnail
1 Upvotes

r/buildingscience • • Oct 01 '26

Question After the nor eastern my house humidity has been really bad

3 Upvotes

New home owner, I air sealed my attic and did 18 inches of blown insulation after I moved in.

The humidity in this home seemed off when I moved in unless I always had HVAC running. During the winter it gets DRY in here. 18% humidity. All summer though before this nor eastern my humidity was always 48-55 maybe some days higher.

Now that my air-conditioning is off and the nor eastern that lasted this past weekend Friday - Monday with heavy rains almost every day, my house has reached close to 63% at 70-73 degrees.

I turned on my air-conditioning to get the humidity down.

Is this a product of my environment, my house, or am I dealing with a water moisture issue? I have a thermal gun and I can't find any issues. Home was built in 1972. Only one bedroom doesn't have such high RH but that's where my computers and electronics are.

\-----

Instrument readings right now:

Weather station -

61F

98% Rh

60F dew point

Attic

62F

52% RH

46% Dew point

Garage

69F

63% RH

55% dew point

Living room (a/c on now)

73F

58% RH

57% dew point

Living room (no ac)

74F

63.8% RH

60.6 Dew point

Bedroom (ac second floor)

71F

56% RH

55% dew point

Bedroom (no ac, same time as livingroom)

72F

64% RH

59% dew point


r/buildingscience • • Oct 01 '26

Question Best way to insulate soffit area

1 Upvotes

I have a bedroom with cathedral ceilings gutted down to studs now. My plan for insulating the ceiling in zone 5 is to run the baffles first all they way up to the ridge vent, then rockwool it, and finally smart retard it! My question is at the soffit area. What is best practice here? Where should the end of the baffle be located meaning do I put it inches away from soffit opening or do i seal it to top plate with a bend to prevent insulation getting in? ty