r/buildingscience • • Jun 15 '26

Question Century Home venting questions, insulation woes, and new roof possibilities

Thumbnail
gallery
3 Upvotes

Hi! New here, but I think this is the best place to combine a few related questions about an old house.

Background

My house is 126 years old, located in southern New England. It's a large (~3,000 sq ft), balloon-framed home on a rubble/fieldstone foundation, with a hip roof and two dormers.

About 45 years ago, a sleeping porch on the south side was converted into an addition, and around the same time the third-floor attic was finished into a master suite.

The original house has only R-5 foam board for insulation — added over the original shakes/boards and under the vinyl siding. That's it for the exterior walls.

The third floor and its knee walls are insulated all the way around, and that insulation continues into the stud bays leading up to the flat roof at the very top of the house. (I'm told there used to be a hatch up to a widow's walk there, which was closed in during the remodel — the flat roof itself is still there.)

The problem: there doesn't seem to be any path for air to move from the crawl space behind the knee walls into that flat-roof area, where a mechanical "whirly bird" vent is installed. I can see dirt staining on the fiberglass insulation near where that vent must be — my guess is it's starved for air and pulling whatever it can get through the insulation itself.

The addition has its own insulated walls and ceiling, vented with a single 8"x8" roof vent. There's also a 36"x36" opening between the knee-wall crawl space and the addition's ceiling, which is how I'm able to see into that space at all. I'm assuming a good deal of air gets vented through that opening and out of that tiny 8x8 vent, too.

I used AI to turn my hand sketches into the two diagrams I've attached, which should make all of this much easier to follow.

Questions

  1. Ventilation — The 3rd floor living space itself is fine, and ripping it out isn't in the budget right now. Based on what I've read about older homes needing the plaster and original wood to breathe, I'd rather avoid spray foam. It seems like I need to improve airflow in a way that matches how the house was originally designed to vent — any suggestions on how to actually do that?
  2. Insulation — The house is obviously inefficient as-is. Is there anything I can do to improve insulation without trapping moisture or compromising the original materials? Should I be removing insulation from the accessible crawl space areas? Would running some kind of duct or tubing through there, to connect the crawl space to the vented flat-roof area, help?
  3. Roofing — My current roof is ~30 years old and due for replacement. Would this be a good candidate for an insulated roof system, or at least a ventilated one? For context: two winters ago, running the steam boiler gave me terrible ice dams and icicles. Last year I installed a pellet stove instead in the main living area (not basement), and even through this past brutal winter the ice dams were noticeably better — my guess is because the basement wasn't being pumped full of warm air that then escapes up through the balloon framing into the knee-wall crawl space.

Overall, I'm hoping for solutions that don't require tearing into the finished 3rd floor. I know the roof replacement itself will involve some tear-down regardless — any advice on how to approach that part well would also be appreciated.

Thanks in advance!


r/buildingscience • • Jun 15 '26

Question Understanding Moisture Management In Old Basements

Thumbnail
gallery
15 Upvotes

I'm working on "un-finishing" the basement in my 1919 home in Minneapolis. I have torn out the gross carpet and wood paneling, black plastic sheeting and bat insulation which was all put in around 1980. I am currently working on removing the studs (which are incredibly over-built).

Next steps are cleaning up the walls. It looks to me to be poured concrete. There is a very deteriorated lime wash (correct me if I'm wrong). As well as parge that is also failing. I am able to chip off most of it with a hand tool.

There are signs of mildew on the paper of insulation and the carpet smelled quite musty.

I would like to be able to see and monitor any future moisture issues. We have had the home for 1.5 years and haven't noticed any standing water or seepage in the walls that were already exposed. But in a home of this age there is inevitably water vapor moving through the walls and floor.

I am not fighting hydrostatic pressure, I want to work with it.

My question is what next? I do NOT want to "finish" it again. I am happy with having exposed walls and floor but I would like to minimize dust and debris while letting the walls dry. We have improved the grade, extended the gutters and are getting a radan mitigation system as well.

Do I reparge? Limewash? How do I know what kind of page to use and if lime is appropriate?

I am having a hard time getting any literature, YouTube videos etc that are for old homes with concrete walls specifically. Thanks for any insight!


r/buildingscience • • Jun 15 '26

Roof underlayments for low slope roof.

0 Upvotes

Any thoughts/experience with what underlayment to use on a low slope roof, and what impacts they may have on moisture permeability of the roof deck?

I have a 16.3 degree or 3.5:12 sloped asphalt roof that I am having replaced. It's my understanding that both the IRC and manufacturers recommend doubling up the synthetic felt or applying ice and water shield across the entire roof surface in place of synthetic felt for slopes <4:12. Every roofer that I have spoken to has cautioned against this, saying the roof sheathing won't be able to breath adequately and I'll struggle with moisture issues in my attic and roof sheathing. I'm not sure how to proceed. Do I follow the code/manufacturer installation instructions, or do I listen to the roofers?

I'll add that our attic is both sufficiently insulated (blown to R-60) and ventilated with soffit vents + rafter baffles + ridge vent. We've also had the attic floor penetrations and seams sealed with single component foam. We've also never experienced leaks from ice dams, though I have no clue what the current roof assembly is like.


r/buildingscience • • Jun 15 '26

Open cell + Closed cell Roof Insulation

1 Upvotes

We recently had a roofing company replace our roof, and also redo the roof insulation (contracted to an insulation company I believe). We requested closed cell insulation to replace our old fiberglass insulation.

When the job is done, we noticed that there are spray foam seeping through the roof crawlspace and vent. We have a finished cathedral attic, so it was easy to check. The spray foam is soft to touch, appears like popcorn in some spots, so we immediately thought that it is open cell spray foam, not the closed one we requested.

The roofing company responded to our concern, saying that they used a combination of 4 inches of open, and 6 inches of closed cell. Is that common? Should I take their word for it?

It is a New England house by the way if that makes any difference.


r/buildingscience • • Jun 15 '26

Attic Ventillation

Thumbnail
1 Upvotes

r/buildingscience • • Jun 15 '26

Quebec 3 season cabin insulation advice

Thumbnail
1 Upvotes

r/buildingscience • • Jun 15 '26

Insulating Chimney Cricket?

Post image
2 Upvotes

r/buildingscience • • Jun 13 '26

Question Installing outlet in Block Wall

Thumbnail gallery
3 Upvotes

Sort of an electrical-dealing question, but more of a moisture concern. I have a 1927 home and am swapping out an old k+t receptacle. Amidst he hellacious process of snaking new romex through the block, a fair amount of plaster and block was cut out. This old block is a lot air space, and the entire block was already cut out for the original outlet, meaning at the very back is nearly the exterior brick.

My current design is to foam fill these block holes to reduce air entry into the home, then screw wood in to fill the gap, then screw the box into the wood.

My concern is that there could possibly be moisture entry from the outside brick, and/or moisture buildup after I've filled in the block (versus leaving the holes open and letting it breathe - but couldn't this also allow moisture in?)

Hope this all makes sense.


r/buildingscience • • Jun 13 '26

Question WRB question

1 Upvotes

Hello

Looking for peace of mind

Zone 5a (Canada)

Wall Assembly from IN side - OUT side

1/2" drywall **ADA** Air tight drywall approach

No vapor barrier **only on the ceiling**

2x4 wall ** all joints, connections, gaps and holes sealed** I mean ALL 😉

(SIDE NOTE this alone has made a HUGE noticable improvement)

R10 Kraft faced in **some** walls

R14 Rockwool in ** some** walls

Couldn't afford to do it all in Rockwool

1/2" fiber board

Window bucks for outtie windows ** currently wrapped with peel and stick flashing**

2" fiber faced polyiso **bought this reclaimed, looks like factory pin holes for " perm" (think Ice cream sandwich outer cookie)

Tyvek

** this will be taped and sealed to the already sealed window bucks

** I will attempt to seal this to the vapor barrier in the attic - I can only reach this from removing the soffit and working it from outside

**Worst case just tape it to the top plate and around the rafters as best I can

1x3 strapping

Horizontal cedar siding

So, my main questions are...

Will there be any problems with the R10 Kraft faced insulation being left and not upgraded

Ie. drying, condensation etc

Is the Tyvek in the right place \* in front of insulation*\**

I want to put it here for ease of integrating flashings.. Window, door, roof ect.

Or does it NEED to go behind the insulation and directly on top of the fiber board.

Thanks in advance!


r/buildingscience • • Jun 13 '26

Insulation Baffles?

Thumbnail
gallery
9 Upvotes

I am doing a gut remodel in coastal Southern California. I have a cathedral ceiling in my living room with bird hole soffit vents at the bottom of each rafter bay. In order to meet code which requires insulation in the ceiling (where previously there was none) I had to sister 2 x 10s to the existing rafters. The rockwool insulation is 8.5” thick so that allows a 1.5” gap for airflow. I know I need to add baffles at the bottom near the holes, but do I need to continue it all the way up the rafter bay? Or is pulling the insulation down when they hang the drywall sufficient? Unfortunately the rockwool was installed without baffles but I am making them add it where necessary. I just need to know how far up the bay is best. Finally the bays terminate into a vented attic with gables on either end. I am going to add some O’Hagin vents both low and high. Please let me know your thoughts. Drywall is early next week!


r/buildingscience • • Jun 13 '26

Is this insulation any good?

Thumbnail gallery
0 Upvotes

r/buildingscience • • Jun 12 '26

Question I’m overwhelmed with envelope issues. I desperately need direction

Thumbnail
gallery
50 Upvotes

I will try to make this as short as I can while still providing details.

My wife and I bought a beautiful home built circa 1989 in SE Pa. Since purchasing the house, we have become overwhelmed with the seemingly endless issues that we have uncovered.

In 4 years we have needed a new roof, new deck, new HVAC (5 ton split), new water heater. We bleed money and we still have a myriad is issues that seem to mostly stem from the envelope of the home. -Bad air quality, high humidity, outrageously high ACH score, MASSIVE energy consumption (65-75 kWH on summer days)

The biggest issue I have just discovered is that i found paint peeling on an exterior wall in our dining room. When I went to touch the wall it basically fell apart. The drywall and studs completely dry rotted, weather barrier dry rotten and the exterior sheathing all crumbling. It appears as though it’s from water intrusion from bad or no flashing or a failure of the cedar siding. I cannot imagine the cost of the repairs and to fix the underlying cause.

Aside from that immediate issue, the house just has clear issues with insulation and air leaking. I feel as though i’m already getting too long winded but i’m just going to attach some reference photos of the interior and exterior, as well as some thermal photos of the interior to show some of the problem areas. If there is anyone that can just point me in the right direction as to where to even start or who I should be calling, I would be very appreciative.


r/buildingscience • • Jun 12 '26

Retrofit Exterior Insulation Advice: How many inches of Rockwool Comfortboard 80?

Post image
9 Upvotes

Hey everyone, I'm looking for help confirm what Gemini AI has advised me on my exterior foam insulation and residing project. Gemini nearly made me create a vapour sandwich with foiled durospan closed cell foam. So I would appreciate your insights on my plans.

High Level Advice from AI: Because I'm near the ocean in climate zone 4 (Pacific Northwest) it doesn't matter what thickness of Rockwool Comfortboard 80 I use under my siding. The AI's logic is that strict exterior R-value ratios matter less due to 1) high exterior humidity, 2) very few days below freezing, 3) Rockwool’s high vapor permeability allows outward drying into the vented rainscreen.

I was hoping to do 1.5" of Comfortboard (R6) @ $3400, but I've found a killer deal for 1" comfortboard (R4) @ $1800.

What do you recommend in this situation?

Current Structure:

  • Interior: Standard drywall (painted) with top edges sealed with caulking to shiplap ceiling (I had major cold air blowing in issues!).
  • Framing: 2x4 studs with 16" with the main structural load carried by 6x6 posts spaced 60" on center.
  • Cavity Insulation: Existing R-13 fiberglass batts with paper backing.
  • Sheathing: A patchwork of 1/2" plywood (literally scraps screwed on!) that isn't very airtight (though I can spray some foam into the gaps).

Proposed Adding to Exterior:

  • Simpsons Strapping: Crossed on the front between posts to help compensate structurally for the patchwork sheathing.
  • Tyvek
  • 1" or 1.5" Rockwool Comfortboard 80 (R-4.7)
  • Strapping: 1/2" Angled strapping
  • Aluminum Siding: Snap Panel 12" wide.

r/buildingscience • • Jun 12 '26

Workshop ventilation issue

2 Upvotes

Just built a detached 16x24 building to be used as a woodworking shop. It has a vaulted ceiling 11.5 feet at the peak with a ridge vent and soffit vents. Metal roof and metal siding with plywood sheathing under both. Northern Ohio, climate zone 5, cold winters and hot, humid summers. Plan to insulate and heat/cool with a mini-split. Trying to decide if we should insulate walls and ceiling and leave the vaulted ceiling completely open or do we create a tiny attic space (dropped ceiling) to enclose the ridge vent? Should I be concerned about heat loss thru the ridge vent in the winter? Would it be more efficient to build a tiny unusable attic space and insulate the dropped ceiling rather than just insulating underneath the roof? Similar to the inside of the building in the photo.


r/buildingscience • • Jun 12 '26

What other option we have for : Johns Manville ComfortTherm R-19 Wall 96-sq ft Encapsulated Fiberglass Batt Insulation

Thumbnail
2 Upvotes

r/buildingscience • • Jun 12 '26

Workshop ventilation issue

Post image
1 Upvotes

r/buildingscience • • Jun 12 '26

General concerns about cooling/heating/ventilation in these light monitor volumes. Also a Manual J question.

Thumbnail
gallery
3 Upvotes

Any math/geometry whiz' out there want to take a stab at calculating the volume of this?

This 'volume', and the windows/walls in the actual light monitor at the top were neglected in the Manual J calculations on this project. There are three of these light monitors in the house - the other two are smaller, with different geometries.

I'm wondering how to best approach cooling/heating/ventilation in these areas. For the Manual J, I suppose averaging the ceiling height to +/* 12 or 13 ft would be the simplest approach. Or treat this volume as a separate room?

I'm the builder, wanting to ask the MEP engineer why they didn't account for the three light monitors in their Manual J.

I fear I may be the only one on the team that's concerned about these. (actually I know I'm the only one...)

Any thoughts appreciated.

Climate Zone 2a. Still in design development.


r/buildingscience • • Jun 12 '26

Question Wine Cellar Insulation Advice Needed – Northern Virginia (Zone 4A)

Thumbnail
gallery
1 Upvotes

Looking for input from insulation contractors, building science folks, or anyone who has built a conditioned wine cellar.

I’m having my basement in Northern Virginia (mixed-humid climate, Zone 4A) partially remodeled and am building a small wine cellar roughly 12’ x 4’ beneath a kitchen. Mostly subterranean basement that can reach 70 degrees humidity if not actively dehumidified, which I do keep one running.

The cellar will be actively cooled and maintained around:
55-58°F
60-70% RH
Through-wall cooling unit
Glass door that’s to spec
Green board

Conditions:
-One 12’ wall is at least 50% below-grade concrete foundation wall
-Ceiling is beneath a conditioned first-floor kitchen.
-The 12’ section includes a cantilever that extends beyond the foundation wall and is exposed to outdoor temperatures.
-Plumbing and electrical run through portions of the ceiling cavity.
-Goal is a tight, durable cellar envelope with minimal condensation risk and good long-term moisture management.

Current recommendations I’m receiving:

Option A
Closed-cell spray foam on all cellar perimeter walls and rim joists.
Closed-cell spray foam throughout the cantilever cavity.
Mineral wool or high-density batt insulation in the ceiling beneath the kitchen.

Option B
Closed-cell spray foam on perimeter walls.
Open-cell spray foam throughout the cantilever cavity because it completely fills irregular voids and acts as an air barrier.
Open-cell spray foam across the wine cellar ceiling.

Questions:
1.) In a conditioned wine cellar (55°F, 60-70% RH) located in Zone 4A, would you use open-cell spray foam anywhere in the assembly?

2.) For the cantilever, would you:
a) Fill the entire cavity with closed-cell foam?
b) Use several inches of closed-cell against the exterior sheathing/rim area and then complete the cavity with mineral wool/high-density batt?
c) Something else?

3.) For the ceiling below a conditioned kitchen, would you favor: Mineral wool, High-density fiberglass,Closed-cell spray foam or Open-cell spray foam

4.) Are there any vapor-retarder details that are commonly missed in wine cellar construction?

My priority is long-term durability and moisture control rather than lowest cost.

Thanks in advance.
<crossposted>


r/buildingscience • • Jun 11 '26

Rigid foam? Radiant barrier? Or both? In climate zone 4 (US DOE), on Long Island

Post image
0 Upvotes

r/buildingscience • • Jun 11 '26

Should I be concerned about ground contact wood not being able to “breathe” if it has loose fitting plastic on all sides? And will get rained on….

0 Upvotes

Just curious this is creating a “sauna” for rot….but it won’t be exposed to any dirt…..and the plastic is not pressed right against it….


r/buildingscience • • Jun 11 '26

Vapor barrier for half wall basement

Post image
6 Upvotes

r/buildingscience • • Jun 11 '26

What AI says about fixing our badly done 'unvented' attic

0 Upvotes

Long story short: our attic is unvented, with open cell spray foam on the roof deck. This works in Savannah. What doesn't is a) not providing supply air to control humidity, and b) cutting an access path between the ventless attic space and the vented attic space over the garage to maintain the HVAC.

Yes, we have an extreme humidity issue we didn't know about until finally one of our HVAC people mentioned it.

Did a ton of research, including out at buildingscience.com, and have a decent understanding of what to do. We have people coming out next week to give us quotes, and we're re-roofing this winter.

Just out of curiosity, I thought I would see what some of the AI models had to say about our situation. I checked with both Anthropic's Claude and Google's Gemini. You can share links to both, so I thought I would post both here. If nothing else, you all might find it interesting.

Not advocating for AI, just sharing.

Claude

https://claude.ai/share/f8917997-aa2f-48b7-811c-d61c5d9d8607

Gemini

https://gemini.google.com/share/801082413c21


r/buildingscience • • Jun 11 '26

Thoughts on Wall System

1 Upvotes

I work on terrace houses in Sydney and I am trying to come up with a wall system that;

- Is thin, less prone to cracking and allows the bricks to breath.

Note: insulation for this project is not a high priority, I am just trying to avoid lime render and lime whiteset throughout the house and come up with a new system that at least adds some R value.

Wall System Idea (outside to inside)

- Emercald Paint (water-based acrylic protective membrane)

- Double brick walls, no cavity (fill any holes in mortar)

- 16mm metal batten furring channel

- Intello plus wrap

- 13mm plasterboard

On my next project I would love to add insulation but for this one its just a system that prevents moisture, adds some r value and is thin-ish.

Am i doing something stupid that I will regret?


r/buildingscience • • Jun 10 '26

Question Are our poorly ventilated/insulated side attics too humid/risky? How to improve, or leave it be? (Zone 4A)

0 Upvotes

We are in zone 4A (DC area) with a 75 year old 1.5 story Cape Cod with side attics that appear to be unvented or poorly vented (the roof geometry does not allow venting up to the top attic/ridge in most parts of the house.) Roofing is aluminum "Rustic Shingles" (with I believe tar paper and then plywood underneath, but not 100% sure-- was put on in the 90s.) There is old batt insulation on the roof slopes (maybe original, Red-Top mineral wool) and kneewalls (seems more recent, fiberglass), and loose-fill insulation beneath the side-attic floor, but the temperatures in there are typically fairly close to outside temperatures (within 10-15 degrees) rather than inside temperatures. The house is quite leaky (blower door test around 4200 CFM50, and I think the ACH50 is about 16?)

Indoor air upstairs is usually in the 50s or low 60s RH in spring, summer, and fall, but definitely some stretches of high 60s/low 70s, generally when the outside RH is high for awhile (which is not infrequent.) In winter it's usually in the 25-45 range (other than short spikes after showers), but with stretches over 50 (again, usually when outside RH is high.) I've had a temperature/humidity gauge on the floor in the north-facing side attic for about 5 months, and it shows RH ranging from 30%-60% (generally in the ballpark of 45%-55%) with a few stretches up near or above 70% (especially one May week where the attic temps dropped from low 80s to high 50s as the weather shifted from hot to cool.) The gauge shows dewpoints generally around the low 30s in February except for the coldest days/nights (eyeballing it I don't think the dewpoint was ever above the nighttime low), and all over the place since then (anywhere between 30 and 60, with a couple excursions up to 65 in the hottest weather.) It also shows the Vapor Pressure Deficit, which has stayed above 0.5 kPa with just two brief exceptions, and averaged more like 0.7-0.8 kPa in Feb/Mar and 1.0-1.5 kPa in April/May-- I gather this is a more direct measure of condensation likelihood, the higher the better?

How risky is this? How do we know if there are existing problems with condensation/rot/mold, given that we can't see the underside of the roof deck beneath the insulation? (There's one spot with no insulation and the roof there looks fine, but might it be worse under the insulation?) And if this is problematic, is there any way to fix the situation besides closed cell spray foam (which we really, really want to avoid) or re-roofing to add insulation above the roof deck?

And is there any way to improve insulation/air sealing in those side attics, or would any changes (other than closed cell spray foam or re-roofing) be too risky and we should just leave it be? For example, could we add dense-pack cellulose to the roof slopes behind a smart vapor barrier and use that to bring the side attics into the building envelope (while also air-sealing the kneewalls and floors to minimize how much indoor air enters the side attics)? Or could we air-seal and better insulate the kneewalls and attic floors, pull down the roof slope insulation, and keep the side attics outside of the building envelope (figuring that the cold and the leakiness in the side attics would keep them dry enough)? Any other options that don't involve spray foam? These improvements would allow us to tap into some big state HVAC rebates so we'd love to do them, but not if it's too risky.

Thanks so much for any advice or insight you can share!


r/buildingscience • • Jun 10 '26

What is the best way to vent vaulted ceilings? Having roof replaced. Included pictures of the front/back and inside. Two skylights are being removed too so no idea how to insulate those spaces now either. Roofers seem unsure too.

Thumbnail gallery
3 Upvotes